Pin assignment of the BaseUnit
Table 3- 1
Pin assignment of BaseUnit BU15-P16+A10+2B, BU type A0
Designation
SIN/COS differential
encoder with or without
signal N
Encoder signal A
Encoder signal B
Encoder signal N
Encoder supply 5 V DC
Encoder supply ground
Supply voltage 24 V DC
Shield
Supply voltage L+/M
You connect the supply voltage to terminals L+ and M on a light BaseUnit. For a dark
BaseUnit, the supply voltage of the module to the left is used. An internal protection circuit
protects the F-TM Count module from reverse polarity of the supply voltage. The F-TM Count
module monitors whether the supply voltage is connected.
Encoder supply
The encoder supply from the F-TM Count module provides 5 V DC encoder sensor supply
voltage. The encoder supply is only switched off during the following occurrences:
• There is a fatal error
• There is a firmware update in progress
Note
The F-TM Count module can only support 5 V DC encoders using the module's internal sensor
supply. However, 10 to 30 V DC incremental encoders can be supported when externally
powered.
ET 200SP F-TM Count 1x1Vpp sin/cos HF (6ES7136-6CB00-0CA0)
Equipment Manual, V1.0, 01/2021, A5E47073911-AA
Signal name
A
1
B
3
N
5
7
9
11
5 VDC
13
M
15
L+
View
Signal
name
2
4
6
8
10
12
14
16
3.1 Wiring and block diagram
Designation
A/
Encoder signal A/
B/
Encoder signal B/
N/
Encoder signal N/
U
Encoder supply ground
S1
M
Ground for supply voltage
Shield
Connecting