Siemens SIMATIC ET 200SP Manual

Digital output module rq 4x120vdc-230vac/5a no st(6es7123-6hd00-0bb0)
Hide thumbs Also See for SIMATIC ET 200SP:

Advertisement

Advertisement

Table of Contents
loading

Summary of Contents for Siemens SIMATIC ET 200SP

  • Page 2 ___________________ Digital output module Preface RQ 4x120VDC-230VAC/5A NO ST ___________________ Documentation guide (6ES7132-6HD00-0BB0) ___________________ Product overview SIMATIC ___________________ Wiring up ET 200SP ___________________ Digital output module Parameters/address space RQ 4x120VDC-230VAC/5A NO ST ___________________ (6ES7132-6HD00-0BB0) Interrupts/diagnostics alarms ___________________ Manual Technical specifications Parameter assignment and structure of the parameter data record...
  • Page 3 Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
  • Page 4: Preface

    Siemens recommends strongly that you regularly check for product updates. For the secure operation of Siemens products and solutions, it is necessary to take suitable preventive action (e.g. cell protection concept) and integrate each component into a holistic, state-of-the-art industrial security concept.
  • Page 5: Table Of Contents

    Table of contents Preface ..............................4 Documentation guide ..........................6 Product overview ............................ 8 Properties ............................8 Wiring up .............................. 10 Terminal assignment ........................10 Block diagram ..........................11 Parameters/address space ........................12 Parameters ........................... 12 Explanation of the parameters ..................... 13 Address space ..........................
  • Page 6: Documentation Guide

    Documentation guide The documentation for the SIMATIC ET 200SP distributed I/O system is arranged into three areas. This arrangement enables you to access the specific content you require. Basic information The System Manual and Getting Started describe in detail the configuration, installation, wiring and commissioning of the SIMATIC distributed I/O system.
  • Page 7 Documentation guide Manual Collection ET 200SP The Manual Collection contains the complete documentation on the SIMATIC ET 200SP distributed I/O system gathered together in one file. You can find the Manual Collection on the Internet (http://support.automation.siemens.com/WW/view/en/84133942). My Documentation Manager The My Documentation Manager is used to combine entire manuals or only parts of these to your own manual.
  • Page 8: Product Overview

    Product overview Properties Article number 6ES7132-6HD00-0BB0 View of the module Figure 2-1 View of the module RQ 4×120VDC-230VAC/5A NO ST Digital output module RQ 4x120VDC-230VAC/5A NO ST (6ES7132-6HD00-0BB0) Manual, 07/2014, A5E03576775-AB...
  • Page 9 ● Color identification labels ● Reference identification label ● Shield connector See also You will find additional information on the accessories in the ET 200SP distributed I/O system (http://support.automation.siemens.com/WW/view/en/58649293) system manual. Digital output module RQ 4x120VDC-230VAC/5A NO ST (6ES7132-6HD00-0BB0) Manual, 07/2014, A5E03576775-AB...
  • Page 10: Wiring Up

    • The AUX terminals may only be used with an associated identical voltage or PE. See also You will find additional information on the BaseUnit types in the ET 200SP distributed I/O system (http://support.automation.siemens.com/WW/view/en/58649293) system manual. Digital output module RQ 4x120VDC-230VAC/5A NO ST (6ES7132-6HD00-0BB0) Manual, 07/2014, A5E03576775-AB...
  • Page 11: Block Diagram

    Wiring up 3.2 Block diagram Block diagram Block diagram Figure 3-1 Block diagram RQ 4×120VDC-230VAC/5A NO ST Digital output module RQ 4x120VDC-230VAC/5A NO ST (6ES7132-6HD00-0BB0) Manual, 07/2014, A5E03576775-AB...
  • Page 12: Parameters/Address Space

    Parameters/address space Parameters Parameters for RQ 4x120VDC-230VAC/5A NO ST The effective range of the parameters depends on the type of configuration. The following configurations are possible: ● Central operation with an S7-1500 CPU ● Distributed operation on PROFINET IO in an ET 200SP system ●...
  • Page 13: Explanation Of The Parameters

    Determines whether a channel is enabled or disabled. Reaction to CPU STOP / substitute value Specifies the behavior of the module if the CPU changes to STOP. See also ET 200SP distributed I/O system (http://support.automation.siemens.com/WW/view/en/58649293) Digital output module RQ 4x120VDC-230VAC/5A NO ST (6ES7132-6HD00-0BB0) Manual, 07/2014, A5E03576775-AB...
  • Page 14: Address Space

    Parameters/address space 4.3 Address space Address space Configuration options The following configurations are possible: ● Configuration 1: Without value status ● Configuration 2: With value status Evaluating the value status An additional byte is allocated in the input address space if you enable the value status for the digital module.
  • Page 15: Interrupts/Diagnostics Alarms

    Interrupts/diagnostics alarms Status and error display LED display The figure below shows the LED displays of the RQ 4x120VDC-230VAC/5A NO ST. ① DIAG (green/red) ② Channel status (green) ③ PWR (green) Figure 5-1 LED display Digital output module RQ 4x120VDC-230VAC/5A NO ST (6ES7132-6HD00-0BB0) Manual, 07/2014, A5E03576775-AB...
  • Page 16 Interrupts/diagnostics alarms 5.1 Status and error display Meaning of the LED displays The following tables show the meaning of the status and error displays. Measures for dealing with diagnostics alarms can be found in the section Diagnostics alarms (Page 17). DIAG LED Table 5- 1 DIAG LED fault/error display...
  • Page 17: Interrupts

    Interrupts/diagnostics alarms 5.2 Interrupts Interrupts The RQ 4×120VDC-230VAC/5A NO ST digital output module supports diagnostic interrupts. Diagnostics interrupt The module generates a diagnostics interrupt for the following events: ● Channel temporarily unavailable ● Parameter assignment error ● No load voltage Diagnostics alarms A diagnostics alarm is output for each diagnostics event and the DIAG LED on the module flashes.
  • Page 18: Technical Specifications

    Technical specifications Technical specifications Technical specifications of the RQ 4×120VDC-230VAC/5A NO ST 6ES7132-6HD00-0BB0 Product type designation RQ 4x120VDC-230VAC/5A NO ST General information Firmware version V1.1 Usable BaseUnits BU type B0 Color code for module-specific color identification label CC00 Product function I&M data Yes;...
  • Page 19 Technical specifications 6.1 Technical specifications 6ES7132-6HD00-0BB0 Digital outputs Switching frequency With resistive load, max. 2 Hz With inductive load, max. 0.5 Hz With lamp load, max. 2 Hz Total current of the outputs Max. current per module 20 A Total current of the outputs (per module) Horizontal installation 20 A up to 50 ℃, max.
  • Page 20 Technical specifications 6.1 Technical specifications 6ES7132-6HD00-0BB0 Electrical isolation Electrical isolation of channels Between the channels Between the channels and the backplane bus Between the channels and the supply voltage of the electronics Permitted potential difference Between different circuits 75 VDC / 60 VAC (basic isolation) Insulation Insulation tested with 707 VDC (type test)
  • Page 21 The following figure show the load current derating with horizontal and vertical mounting positions. Figure 6-1 Load current and mounting position Dimension drawing See manual ET 200SP BaseUnits (http://support.automation.siemens.com/WW/view/en/58532597/133300) Digital output module RQ 4x120VDC-230VAC/5A NO ST (6ES7132-6HD00-0BB0) Manual, 07/2014, A5E03576775-AB...
  • Page 22: Switching Cycles

    Technical specifications 6.2 Switching cycles Switching cycles Switching capacity and lifetime of the contacts With an external protective circuit, the contacts will last longer than specified in the table. This table shows the switching capacity and lifetime of the relay contacts: Table 6- 1 Switching capacity and lifetime of the relay contacts Resistive load...
  • Page 23: Parameter Assignment And Structure Of The Parameter Data Record

    Parameter assignment and structure of the parameter data record Parameter assignment and structure of the parameter data record Parameter assignment in the user program You can change the parameters of the module in RUN. Changing parameters in RUN The "WRREC" instruction is used to transfer the parameters to the module using data record 128.
  • Page 24 Parameter assignment and structure of the parameter data record A.1 Parameter assignment and structure of the parameter data record Header information The figure below shows the structure of the header information. Figure A-2 Header information Parameters The figure below shows the structure of the parameters in data record 128. You enable a parameter by setting the corresponding bit to "1".

Table of Contents