11.2.4 Use example of variable analog potentiometer

1. Example 1
The current value of VR1 is used as the set value of a timer (T0).
2. Example 2
The current value of VR2 multiplied by "10" is used as the set value of a timer (T1).
M8000
RUN monitor
100
D8030 • • • The current value of VR1 is used as the set value of the timer T0.
T0
The setting range in this example using T0 (100 ms timer) in from 0 to 25.5 sec.
FNC 22
D8031
K10
MUL
D0 • • • • • • • • • • • • • • • • • • • • • • • The current value of VR2 multiplied by "10" is used as the
T1
11.2 Built-in variable analog potentiometer function
• • •
The value of D8031 is multiplied by "10", and stored in
D0 (D1)
D0 (D1).
set value of the timer T1.
The setting range in this example using T1 (100 ms timer)
is from 0 to 255 sec.