17.6 Connections to the outdoor unit

17.6.1 Low voltage wiring – Outdoor unit
LRYEN10A7Y1+LRNUN5A7Y1
CO₂ Conveni-Pack outdoor unit
4P605460-1 – 2020.08
NOTICE
Be sure to keep the power line and transmission line apart from each other
(≥50 mm). Transmission wiring and power supply wiring may cross, but may not
run parallel.
Transmission wiring and power supply wiring may NOT touch internal piping in
order to avoid wire damage due to high temperature piping.
Firmly close the lid and arrange the electrical wires so as to prevent the lid or
other parts from coming loose.
Low voltage wiring
High voltage wiring
Connections/routing/fixing
X1M (A1P)
X5M
d/e
X1M (A1P)
DIII transmission wiring:
a: To capacity up unit
b: To indoor units (air conditioning)
c: To communication box
X5M
Remote switches:
d: Remote operation switch
e: Remote low noise switch
1
DIII transmission wiring
Remote switches (operation, low noise)
Output signals (caution, warning, run,
operation)
Power supply (including earth)
TO
IN/D UNIT
F1
1
a
b
2
a/b/c
X1M (A1P)
X5M
17
Electrical installation
|
X1M (A1P)
TO
TO
OUT/D UNIT
MULTI UNIT
F2
F1
F2 Q1 Q2
c
X5M
1
2
3
d
e
2
f
Installer and user reference guide
93

Advertisement

Table of Contents
loading

This manual is also suitable for:

Co2 conveni-pack lrnun5a7y1

Table of Contents