20.2.3 Field setting components
LRYEN10A7Y1+LRNUN5A7Y1
CO₂ Conveni-Pack outdoor unit
4P605460-1 – 2020.08
a
d e
d
OFF
a
Outdoor unit
b
Capacity up unit
c1
Inspection hole
c2
Inspection hole cover
d
Operation switch (S1S)
e
Field setting components
7‑segment displays: ON (
e1
e2
Push buttons:
BS1: MODE: For changing the set mode
BS2: SET: For field setting
BS3: RETURN: For field setting
e3
DIP switches
4 After making the field settings, reattach the inspection hole covers and the
front plate.
NOTICE
Close the cover of the electrical component box before turning ON the power.
DIP switches
Use DS1 to set the target evaporating temperature for the refrigeration side. Do
NOT change DS2.
DS1
DS2
ON
ON
OFF
OFF
1 2 3 4
1 2 3 4
Normal load
ON
OFF
1 2 3 4
(b)
ON
OFF
1 2 3 4
ON
OFF
1 2 3 4
ON
OFF
1 2 3 4
ON
OFF
1 2 3 4
(a)
For low load restrictions, see
(b)
Factory setting
c1
b
d e
c2
e
DS1
ON
OFF
1 2 3 4
) OFF (
) Flashing (
)
DS1
(a)
Low load
ON
OFF
1 2 3 4
ON
OFF
1 2 3 4
ON
OFF
1 2 3 4
—
—
"14.5.2 Constraints for
20
Configuration
|
e1
e2
DS2
e3
ON
OFF
1 2 3 4
Target evaporating
temperature
–10°C
–20°C
–15°C
–5°C
0°C
4
refrigeration" [
49].
Installer and user reference guide