Supported Data Formats - Siemens SENTRON 7KN POWERCENTER 3000 Manual

Iot data platforms
Hide thumbs Also See for SENTRON 7KN POWERCENTER 3000:
Table of Contents

Advertisement

5.9.1.2

Supported data formats

Value
format
Unsigned
Depending on the number of bytes or bits If both values = 0, the entire number of registers (one register is
equal to two bytes) is interpreted as unsigned
Signed
Depending on the number of bytes or bits If both values = 0, the entire number of registers is interpreted as
signed
Floating
If the data point is defined as 2 registers, floating point 32 bits is used.
point
If the data point is defined as 4 registers, floating point 64 bits is used.
ASCII text
ASCII text
Time stamp
Time stamp
7KN POWERCENTER 3000
Equipment Manual, 07/2020, L1V30579222003-03
Description
Functions
5.9 Modbus devices
85