Siemens SENTRON 7KN POWERCENTER 3000 Manual page 34

Iot data platforms
Hide thumbs Also See for SENTRON 7KN POWERCENTER 3000:
Table of Contents

Advertisement

Installing, connecting, commissioning
4.3 Connecting the device
Note
The 24 VDC power supply must meet the voltage requirements specified in Technical data
(Page 123).
Requirements
• The ground conductor has been connected.
• You are using the terminal provided.
• A two-wire cable with a conductor cross-section for the 24 V DC connection of 0.75 mm
to 2.5 mm
• A flat-tip screwdriver with an approx. 3 mm (1/8 in.) blade.
Procedure
32
(18 - 12 AWG).
2
1.
Switch off the 24 V DC power supply.
2.
Connect the power supply cables to the
marked position.
3.
Connect the terminal to the marked posi-
tion.
Equipment Manual, 07/2020, L1V30579222003-03
2
7KN POWERCENTER 3000