B7AH
I/O Delay: Normal Speed
Connection of Independent Power Supplies
Input side
5 VDC
Connection of Single Power Supply to Input or Output Terminal
Input side
5 VDC
I/O Delay: High Speed
Connection of Independent Power Supplies
Input side
5 VDC
Connection of Single Power Supply to Input or Output Terminal
Input side
5 VDC
Output side
12 to 24 VDC
5 VDC
Transmission distance: 500 m max.
5 VDC
24 VDC
Transmission distance: 100 m max.
12 to 24 VDC
5 VDC
Shielded cable
Transmission distance:
GND
100 m max.
5 VDC
Shielded cable
24 VDC
Transmission distance:
GND
50 m max.
12 to 24 VDC
Note: A VCTF cable with a thickness of 0.75 mm
min. must be used for signal transmission.
Output side
Note: A VCTF cable with a thickness of 0.75 mm
Output side
Note: In this example, a shielded cable with a
12 to 24 VDC
Output side
Note: In this example, a shielded cable with a thick-
min. must be used for signal transmission.
A current of 1.8 A max. can be transmitted
along the power line (+, –).
2
thickness of 0.75 mm
min. is used for
signal transmission. It is recommended
that the shield be grounded.
The maximum transmission distance is
10 m if a VCTF wire with a thickness of
2
0.75 mm
is used instead of a shielded
cable for the transmission path.
2
ness of 0.75 mm
min. is used for signal
transmission. A current of 1.8 A max. can be
transmitted through the power line (+, –). It is
recommended that the shield be grounded.
(Do not connect to a negative pin.)
The maximum transmission distance is 10 m
if a VCTF wire with a thickness of 0.75 mm
is used instead of a shielded cable for the
transmission path.
B7AH
2
2
2
69