B7A
Output Models
Item
Output configuration
Current consumption
(see note)
Rated load voltage
Output residual voltage
Output current
Error output
Mounting strength
Terminal strength
Tightening torque
Weight
Note: Consumption when all 16/32 points are ON. Excludes external load current and error load current for Output Terminals.
Nomenclature
16-point Terminal Models
I/O connector
32-point Terminal Models
I/O connector
34
16-point
B7A-R6A13/R6A18/R6A33/R6A38
NPN open collector
50 mA max. with all input terminals ON
5 to 24 VDC
0.8 V max.
Sync. current, 50 mA max./point
Rated load voltage: 0 to 30 VDC
Output current:
sync. current, 100 mA max./point
No damage when 49-N pull is applied for 1 min each in all directions
No damage when 49-N pull is applied for 1 min each in all directions
0.78 to 1.18 N m
Approx. 46 g
OUTPUT SELECTOR
(Output Unit only)
Selector 2
(Output Unit only)
Selector 1
(Output Unit only)
B7A-R3A13/R3A33/R3A18/R3A38
80 mA max. with all input terminals ON
Approx. 71 g
Power terminals
Power and error indicator
(also used as a terminal insulator)
Transmission
terminals
Power terminals
Transmission
terminals
32-point
Power indicator (also used
as a terminal insulator)
ERR1 indicator (also used
as a terminal insulator)
ERR2 indicator (also used
as a terminal insulator)
B7A