B7AP
Note: 1. The maximum I/O points refers the maximum I/O points handled simultaneously by the B7A Input and Output Units. Figures in
parentheses indicate the maximum I/O points handled simultaneously by the B7A Input and Output Units each connected with an
independent power supply. Refer to Power Supplies on page 110.
2. The maximum I/O points are the same as the maximum input points of the B7A Input Unit connected to the B7AP-M1.
3. PLCs and three-wire sensors can be connected only if the B7A Input and Output Units are each connected with an independent
power supply. Refer to Power Supplies on page 110.
Specifications
Communications Specifications
Communications method
Transmission distance (couplers)
Transmission distance (B7A)
I/O delay time
Minimum coupler interfacing time
Minimum distance between Power
Couplers mounted in parallel
Note: 1. The value is for the case where a power supply is provided only for the B7AP-S1.
2. Minimum coupler interfacing time is the minimum time required for signal and power transmission between the B7AP-S1 and
B7AP-M1 Power Couplers.
Characteristics
Item
Power supply voltage
Current consumption
Insulation resistance
Dielectric strength
Noise immunity
Vibration resistance
Shock resistance
Ambient temperature
Ambient humidity
Cable pulling strength
Nut tightening strength
Enclosure rating
Maximum cable length
Weight
EMC
Approved standards
Moving Unit Specifications
Output voltage
Output current
Note: Use the Moving Unit so that the total current consumption of all input devices is 38 mA max. if power is supplied to the input devices
through the Moving Unit.
108
Unidirectional, time-division multiplex
8 1.5 mm
100 m max. (see note 1)
Typical:
19.2 ms; 31 ms max.
0.3 s (see note 2)
60 mm
B7AP-S1
24 VDC 10%
300 mA
100 MΩ min. (at 500 VDC) between each lead wire and external parts
1,000 VAC, 50/60 Hz for 1 min between each lead wire and external parts
Noise level: 1.5 kV; pulse width: 100 ns to 1 µs (on transmission line due to coupling)
10 to 55 Hz, 1.5-mm double amplitude
2
500 m/s
Operating: –10 to 55 C (with no icing or condensation)
Storage:
–25 to 65 C (with no icing or condensation)
Operating: 35% to 95% (with no condensation)
49 N
39 N m
IEC IP67
2 m
Approx. 300 g
Radiated Emissions:
Radiated Immunity:
Electrostatic Discharge:
Burst Transients:
UL508
Conforms to EN50081-2, EN50082-2
12 VDC 10%
38 mA
---
---
Approx. 230 g
EN55022 class A
prEN50082-2
prEN50082-2
prEN50082-2
B7AP