Pentair Pentek Intellidrive PID10 Installation And Operation Manual page 8

Hide thumbs Also See for Pentek Intellidrive PID10:
Table of Contents

Advertisement

Available languages

Available languages

INSTALLATION
PUMP CONNECTIONS
If the Pentair Pentek Intellidrive ® Constant Pressure Pump
Controller is used with above ground motors (3-phase only) not
rated for Variable Frequency Intellidrive use, maximize motor
life by limiting lead length to 25 ft. Refer to the pump's owner's
manual, the National Electrical Code, and local codes for proper
wire size.
The output of the Intellidrive is single phase (2-wire or 3-wire)
or 3-phase, depending on motor selection during startup. The
output power terminals (motor wire connections) are located
on the lower right side of the Intellidrive and are labeled R (Red),
Y (Yellow), and B (Black).
To select the wire size, multiply the wire length by 0.95 and then
refer to the pump owner's manual, the Nation Electric Code, and
local codes for proper wire size.
Regardless of owner's manual, wire LENGTH may not
NOTE:
exceed 1000 ft. (305 M).
2-wire 1-phase connect to Y+B, not R+B.
NOTE:
01+ 01+ I1+ I1- I2+ I2- V+ V- AI+ AI- P N SD CARD
Terminal
Removable
(pull down)
Input Power
Connections
8
Green Cable Shield/Screw
Input
Input
Ground Screw
Ground
Figure 8 - Basic Wiring Connections
FAN
The Intellidrive uses a thermostatically controlled internal
fan which operates automatically when necessary to cool the
Intellidrive components.
Red to AI+
Black to AI–
Transducer Cable
Ground Screw
Connections
Submersible Motor: 3-Ph./ 3-W. 1-Ph., follow colors as above.
Submersible Motor: 1-Ph./ 2-W., connect to Y and B, any order.
Above-Ground Motors: L1 to R, L2 to Y, L3 to B; verify rotation.
5999 0509
Figure 7 - Keyboard Functions
Terminal
Removable
(pull down)
Red
Yellow
Black
Motor Connections
Output
Output Ground
6539 0412
PN957 (25-06-20)