Pentair Pentek Intellidrive PID10 Installation And Operation Manual page 14

Hide thumbs Also See for Pentek Intellidrive PID10:
Table of Contents

Advertisement

Available languages

Available languages

PROGRAMMING
Menu
Parameter
Settings
Excessive Runtime Detection
Ex Runtime
Excessive Runtime Hours
Auto Restart Delay
Number of Resets
Detection Time
Dry Run
Sensitivity
Fill Time
Digital Input 1
Digital Input 2
I/O
Relay Output
Over Press
Over Pressure
No Ground
No Ground Detection
Reset
Factory Reset
SW Update
Software Update
14
Value
Unit of Measure
Default
Min.
_
Disabled
Disabled
Hours
24
Minutes
10 Min
3 Min
3
M:SS
15 Sec
5 Sec
PSI
10
M:SS
1 M
15 S
Unused
Unused
Unused
PSI
80 PSI
15 PSI
Enabled
Disabled
No
No
Disabled
Disabled
Table 5, Continued - Main Menu and Parameters
Max.
Enabled Enables or disables Excessive Runtime Detection.
Number of hours Intellidrive can run before it faults on Excessive
1
100
Runtime.
Time Pentair Pentek Intellidrive ® Constant Pressure Pump
60 Min
Controller waits to restart pump when Dry Run is detected.
Number of tries Intellidrive attempts to restart pump when Dry
0
5
Run condition is detected.
10 Min
Time the Intellidrive takes to recognize Dry Run condition.
Pressure value that Dry Run condition is detected at. Dry Run
0
300
fault will occur if this pressure cannot be met within Detection
Time window. Lower pressure = less sensitivity.
Time allowed to fill (prime) pipes during Auto Line Fill process.
10 M
Relates to Dry Run Sensitivity value. (Time starts after 55 Hz is
reached).
Selects operation of Intellidrive when terminal I1 or I2 is used.
Select between Unused, Run Enabled, Ext Fault, and Setpoint.
The Intellidrive will respond to selected command when voltage is
present at I1 or I2 terminal.
Selects the operation of Intellidrive when terminal O1 is used.
Select between Unused, Run, and Fault. The Intellidrive closes
the Relay when Run or Fault is selected.
Sets Over Pressure Warning value. Change if higher than 80 PSI
97 PSI
system pressure is needed.
Selects whether Ground Detection parameter is Enabled or
Enabled
Disabled. If Disabled is selected, it will revert back to Enabled
after 72 hours. Warning LED will flash entire time it is Disabled.
Resets all parameters to factory defaults. Displays Setup Guide
Yes
after it is complete. Software version displayed here. Does not
clear fault log.
Enabled Used to update software, if necessary.
Description
PN957 (25-06-20)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents