Download Print this page

Pentair Pentek PPC7 Series Quick Start Manual

Variable frequency drive
Hide thumbs Also See for Pentek PPC7 Series:

Advertisement

Quick Links

1
MOUNTING LOCATION
• On the wall:
NEMA 1 rated boxes – interior only
n
NEMA 3R rated boxes – protected outdoor installation.
n
• Mount the VFD vertically and as close as possible to the
main CB panel. 
• Leave 3" Clearance around the VFD for cooling.
2
RUN THE CABLE
• Cables to NEMA 3R rated boxes must be in liquid tight conduit and connectors to maintain the 3R rating.
• The input from the CB Panel must be 8" from motor wiring and 8" from all other house wiring. Maintain the 8" separation when
crossing other wiring.
• Cross all branch circuits at 90°.
• The motor wires should exit the building as soon as possible.
6
PLUMBING/TANK/CABLES
• The tank pre-charge should be 70% of the preset pressure point (42 psi for a 60 psi preset).
293 WRIGHT STREET, DELAVAN, WI 53115 WWW.PumPS.COm
PH: 1-866-9 PENTEK
© 2013 Pentair Ltd. All Rights Reserved.
PPC7 Series Variable Frequency Drive Quick Start Guide
Before you start, be sure you have the correct model for your installation:
1/2, 3/4, and 1 HP use Models PPC7-1-7A3-1-A (NEMA 1) or PPC7-1-7A3-3-A (NEMA 3R)
1-1/2 and 2 HP use Models PPC7-1-13A2-1-A (NEMA 1) or PPC7-1-13A2-3-A (NEMA 3R)
3
CONNECT THE CB PANEL TO THE VFD
• Do not wire to a sub-panel – only to the main breaker panel.
• Ground the VFD back to the building's own ground (that is, to the
system ground from the CB panel, going to the system ground rod).
• Use a dedicated 230V branch circuit directly from the main CB panel:
15 amp CB for Model PPC7-1-7A3.
30 amp CB for Model PPC7-1-13A2.
7
POWER ON!
Pump may start; parameters may be set with the pump running.
NOTE: Check all wiring connections before turning on the power to the VFD.
SET PARAMETERS AT STARTUP
H.P.
Parameter No.
Set To
1/2, 1-1/2
None
None
3/4, 1
9
7.3
9
12.2
2
22
62.0
NOTE: Parameter 9 is used as an example. Set other parameters in the
same manner. To reset Water Pressure Set Point (Parameter 133), see the
Installation Guide.
Step 7.1.A: Push 'MODE' to display parameters.
Step 7.1.B: Turn the knob until the display shows P. 9 (Parameter 9).
Step 7.2.A: Push 'SET' to display the default set point of the selected
parameter.
Step 7.1
Step 7.2
This Quick Start Guide neither supplements nor
replaces the installation guide.
4
CONNECT THE VFD TO THE MOTOR
• Connect the motor leads in the order as shown.
• Connect the motor ground to the inverter's grounding terminal as shown.
• Ground the motor to the well head.
• Ground the VFD to the motor with a dedicated grounding wire; bundle
the ground and motor wires.
8
The system is operational.
Step 7.2.B: Turn the knob to adjust the set point (see table at left).
power wiring before hanging the box. Always hang the VFD box before
Release the knob and push 'SET'. The display will alternate between the
connecting the wires to it.
Parameter Number and the new set point.
Step 7.2.C: Repeat for P. 22 (2 HP only)
service with wet or damp hands. Always make sure your hands are dry before
Step 7.3.A: Push 'MODE' twice to return to the standard display (Hz).
working on the VFD. Perform all dial setting and keying operations with dry hands.
Step 7.3.B: Push 'SET' to display Amps.
Step 7.3.C: Push 'SET' again to display Pressure (PSI).
on to the VFD.
Continuing to push 'SET' will scroll through these three displays (Hz, Amps, PSI).
NOTE: To lock or unlock settings, to display all parameters, and for
detailed information, see the Installation Guide.
circuit breaker protection. To make sure of protection in the event of an internal
fault in the VFD, install the VFD on an independent branch circuit protected by a 15 amp circuit
breaker (Model PPC7-1-7A3, 1/2 to 1 HP) or a 30 amp circuit breaker (Model PPC7-1-13A2, 1-1/2 and
2 HP), with no other appliances on the circuit.
Step 7.3
are connected incorrectly or the wrong voltage is applied. Apply
only the voltage specified to each terminal. Connect cables to the correct terminals as specified in
this guide.
California Proposition 65 Warning
California to cause cancer, birth defects or other reproductive harm.
5
CONNECT THE TRANSDUCER CABLE
• Connect the Transducer Cable as shown.
• Do not disturb the factory installed jumpers.
• Clean out the box: NO DEBRIS!
NOTE: Before connecting the pump to the system, 'pump out' the well to clean
it. Be sure that the transducer is connected to the VFD and sees 0 PSI pressure.
Throttle the pump discharge to reduce the load on the motor. Once the well is clean,
proceed with plumbing the well.
REPLACE THE VFD'S COVER
Risk of electrical shock if VFD is connected to the
Risk of electrical shock if the VFD is handled or
Risk of electrical shock. Do not change the cooling fan while power is
Fire hazard if installed with incorrect or inadequate
Risk of component explosion and fire if the cables
This product and related accessories contain chemicals known to the State of
PN849 (REV 02/25/13)

Advertisement

loading

Summary of Contents for Pentair Pentek PPC7 Series

  • Page 1 Risk of component explosion and fire if the cables are connected incorrectly or the wrong voltage is applied. Apply only the voltage specified to each terminal. Connect cables to the correct terminals as specified in this guide. California Proposition 65 Warning This product and related accessories contain chemicals known to the State of California to cause cancer, birth defects or other reproductive harm. 293 WRIGHT STREET, DELAVAN, WI 53115 WWW.PumPS.COm PH: 1-866-9 PENTEK PN849 (REV 02/25/13) © 2013 Pentair Ltd. All Rights Reserved.
  • Page 2 Guide de démarrage rapide du mécanisme d’entraînement Control de frecuencia variable (“CFV”) à fréquence variable de la série PPC7 de PENTEK PENTEK Serie PPC7 - Guía de Inicio Rápido Avant de commencer, vérifiez que vous avez le modèle qui convient à votre installation : Antes de comenzar, verifique que tenga el modelo correcto para su instalación: Les puissances de 1/2, 3/4 et 1 HP requièrent un modèle PPC7-1-7A3-1-A (NEMA 1) ou PPC7-1-7A3-3-A (NEMA 3R). 1/2, 3/4, y 1 HP usan Modelos PPC7-1-7A3-1-A (NEMA 1) o PPC7-1-7A3-3-A (NEMA 3R) Les puissances de 1-1/2 et 2 HP requièrent un modèle PPC7-1-13A2-1-A (NEMA 1) ou PPC7-113A2-3-A (NEMA 3R).