Mounting and Dismantling
4.5 Installing / mounting / removing 3RW5 HMI
• Observe the coding of the plug and socket
• Lock the connector in the socket
• The HMI connecting cable in the cable duct of the 3RW5 HMI Standard may only be routed
downward.
Make sure that you install the cable in accordance with EMC requirements. For example,
install data cables separately from the motor cable. Connect both sides of shielded cables
over a large surface area.
• Make sure that the locking switch on the rear of the 3RW5 HMI Standard is in the required
position.
You will find further information in chapter 3RW5 HMI Standard (Page 105) .
• Insert the push-in lugs into each side of the enclosure until you hear them engage
the 3RW5 HMI Standard on the wall
Result
You have installed the 3RW5 HMI Standard on a flat surface and can commission it.
4.5.8

Installing the 3RW5 HMI High Feature on a flat surface

Requirements
• Note the mounting positions, minimum clearances and ambient conditions stated on the
data sheet
• 3RW5 HMI High Feature (accessory)
• Level surface, e.g. sufficiently strong mounting plate
• 2 properly executed drill holes with thread or plugs on the level surface. Refer to the drilling
pattern (Page 164).
50
.
.
/
.
Equipment Manual, 09/2020, A5E37108631002A/RS-AC/003
and fix
SIRIUS 3RW51 Soft Starter