Parameter assignment
6.8 Parameterize the response to bus errors and output 13, 14 (ON /
Procedure
1. Press the MODE key during operation for longer than 2 seconds until the STATE / OVERLOAD
LED flickers green and press and hold the MODE key.
2. Switch off the power supply (control supply voltage) of the 3RW51 soft starter for at least
5 seconds. After the 5 seconds have elapsed, you can release the MODE key.
3. Press and hold the MODE and TEST / RESET keys.
4. Switch on the power supply (control supply voltage) of the 3RW51 soft starter again.
When the SOFT TORQUE and RESET MODE LEDs flicker green, the parameterization mode is
active. You can release the MODE and TEST / RESET keys.
5. Select the desired parameter using the MODE key.
You can recognize your selection by the color of the STATE / OVERLOAD LED.
80
LED
STATE / OVERLOAD
Off
Lights up green
Lights up red
Parameters to be changed
No selection
Control via digital input
Output ON / RUN
Equipment Manual, 09/2020, A5E37108631002A/RS-AC/003