Siemens SIRIUS 3RW51 Equipment Manual page 138

Soft starters and solid-state switching devices
Table of Contents

Advertisement

Messages & diagnostics
9.4 Faults and remedial actions of the 3RW51 soft starter
Error
Error
No.
1)
1454
Preset unequal actual
configuration
1466
Switching element L1
failed
1467
Switching element L2
failed
1468
Switching element L3
failed
1479
Phase control failure
1482
Current measuring
range exceeded
138
Cause
There is a difference be‐
tween a real slot and a slot
configured in the SIR‐
IUS Soft Start‐
er ES (TIA Portal).
Switching element defec‐
tive
Error appears without
motor start:
– Motor incorrectly
connected
– Inside-delta circuit
wrongly config‐
ured
– Ground fault
Error appears while
motor is starting:
– Starting voltage
too high
With sensors: The
measured value has
exceeded the range
limits.
With actuators: The
output value has ex‐
ceeded an upper limit.
Remedy
Ensure consistency be‐
tween plugged and config‐
ured module. Possibly the
referenced module has a
wiring error.
After the cause is elimina‐
ted, the error self-acknowl‐
edges.
Switch off the power supply
(control supply voltage) for at
least 5 seconds and switch it on
again. If the fault is still present
proceed as follows:
Please contact Technical
Support (Support Request
(Page 11)).
Check the switching ele‐
ments for L1, L2, and L3
and replace any that are de‐
fective.
Check and correct the wir‐
ing.
Adapt parameters.
Check the interaction between
the module and the sensor or
actuator.
Equipment Manual, 09/2020, A5E37108631002A/RS-AC/003
RESET MODE
Man‐
Re‐
Auto
4)
ual
mote
2)
3)
-
-
-
-
-
-
x
x
-
x
x
-
SIRIUS 3RW51 Soft Starter