5
|
Preparation
5.3.7 Piping length: VRV DX and RA DX
Installer and user reference guide
40
Maximum allowable length
Between outdoor and indoor units.
Actual piping length
(a)
Equivalent length
Total piping length
(a) Assume equivalent piping length of refnet joint=0.5 m and refnet header=1 m (for
calculation purposes).
Maximum allowable height difference (on Hydrobox indoor unit)
H1
≤50 m (40 m) (if outdoor is located below indoor units)
H2
≤15 m
Maximum allowable length after branch
The pipe length from the first refrigerant branch kit to the indoor unit ≤40 m.
Example 1: unit 8: b+c+d+e+f+g+p≤40 m
Example 2: unit 6: b+h≤40 m, unit 8: i+k≤40 m
Example 3: unit 8: i≤40 m, unit 2: c≤40 m
For system containing VRV DX indoor units and RA DX indoor units:
System setup
a
H4
H5
H1
Header
BP box
1~5 RA DX indoor units
135 m
Example 1:
▪
a+b+c+d+e+f+g+p≤135 m
▪
a+b+c+d+k≤135 m
Example 2:
▪
a+i+k≤135 m
▪
a+b+e≤135 m
Example 3:
▪
a+i≤135 m
▪
a+d≤135 m
160 m
300 m
Example 3:
▪
a+b+c+d+e+f+g+h+i≤300 m
b
A
B
c
e
f
BP1
6
k
1
2
3
H2
4
d
g
7
BP2
H6
l
5
RYYQ+RYMQ+RXYQ8~20U7Y1B
4P546228-1A – 2019.10
VRV IV+ heat pump