To Select Refrigerant Branch Kits - Daikin VRV IV+ Installer And User Reference Manual

Table of Contents

Advertisement

F: Piping between refrigerant branch kit and branch selector box (BP box)
G: Piping between branch selector box (BP box) and RA DX indoor unit

5.3.3 To select refrigerant branch kits

RYYQ+RYMQ+RXYQ8~20U7Y1B
VRV IV+ heat pump
4P546228-1A – 2019.10
Pipe Ø (mm)
6.4/9.5/12.7
15.9
19.1/22.2
28.6
34.9
41.3
In case the required pipe sizes (inch sizes) are not available, it is also allowed to
use other diameters (mm sizes), taken the following into account:
-
Select the pipe size nearest to the required size.
-
Use the suitable adapters for the change-over from inch to  mm pipes (field
supply).
-
The additional refrigerant calculation has to be adjusted as mentioned in
"6.7.3 To determine the additional refrigerant
Pipe size for direct connection on branch selector box (BP*) must be based on the
total capacity of the connected indoor units (only in case RA  DX indoor units are
connected).
Total capacity index of
connected indoor units
20~62
63~149
150~208
Example:
Downstream capacity for F=[capacity index of unit 4]+[capacity index of unit 5]
Only in case RA DX indoor units are connected.
Indoor unit capacity index
20, 25, 30
50
60
71
Refrigerant refnets
For piping example, refer to
When using refnet joints at the first branch counted from the outdoor unit side,
choose from the following table in accordance with the capacity of the outdoor
unit (example: refnet joint a).
Minimal thickness t (mm)
amount" [
Piping outer diameter size (mm)
Gas pipe
12.7
15.9
19.1
Piping outer diameter size (mm)
Gas pipe
9.5
12.7
15.9
"5.3.2 To select the piping
5
Preparation
|
0.80
0.99
0.80
0.99
1.21
1.43
4
 64].
Liquid pipe
6.4
9.5
Liquid pipe
6.4
9.5
4
size" [
 31].
Installer and user reference guide
33