Step 6B: To Manually Charge Refrigerant - Daikin VRV IV+ Installer And User Reference Manual

Table of Contents

Advertisement

6.7.7 Step 6b: To manually charge refrigerant

RYYQ+RYMQ+RXYQ8~20U7Y1B
VRV IV+ heat pump
4P546228-1A – 2019.10
If
"
", "
", or "
" appears
"
", or "
" appears
INFORMATION
In case a malfunction code occurred during this automatic charging procedure, the
unit will stop and indicate "
Cooling (middle 7‑segment display indicates " ")
Automatic charging will continue, the 7‑segment display indication shows the
current low pressure value and the status indication "
If the 7‑segment display indication/user interface of indoor unit shows " " code,
charging is almost finished. When the unit stops operating, close valve A
immediately and check whether the 7‑segment display indication/user interface of
indoor unit shows " ". This indicates the automatic charging in cooling program
was finished successfully.
INFORMATION
When the charging amount is little, the "
the "
" code will be displayed immediately.
When the required (calculated) additional refrigerant amount is already charged
before "
" or "
If during the cooling operation for the automatic refrigerant charge the ambient
conditions go beyond the allowable for this operation mode, the unit will indicate
on the 7‑segment display "
in case the outdoor temperature is out of range. In this case, when the additional
refrigerant charging was not finished, step
4
refrigerant" [
 72] has to be repeated.
INFORMATION
When a malfunction is detected during the procedure (e.g, in case of closed stop
valve), a malfunction code will be displayed. In that case, refer to
problems based on error codes" 
Resetting the malfunction can be done by pushing BS1. The procedure can be
restarted from
Aborting the automatic refrigerant charge is possible by pushing BS1. The unit will
stop and return to idle condition.
Perform the test procedure as described in "8 Commissioning" [
The remaining additional refrigerant charge can be charged by operating the
outdoor unit by means of the manual refrigerant charge operation mode:
1 Take all the precautions mentioned in
"8 Commissioning" [
2 Turn on the power of the indoor units and outdoor unit.
Push BS1 to finish the automatic charging
function procedure. The ambient conditions are
favourable to execute the test run.
The ambient conditions are NOT favourable to
execute the test run. Push BS1 to finish the
automatic charging procedure.
" flashing. Push BS2 to restart the procedure.
" code may not be displayed, but instead
" indication appears, close valve A and wait till "
" in case indoor temperature is out of range or "
"6.7.6 Step 6a: To automatically charge
4
[
  116] and solve the malfunction accordingly.
"6.7.6 Step 6a: To automatically charge
4
 108] into account.
6
Installation
|
Then
" intermittent.
" is displayed.
"10.2  Solving
refrigerant" [
4
 72].
4
 108].
4
"7  Configuration" 
[
  84] and
Installer and user reference guide
"
73

Hide quick links:

Advertisement

Table of Contents

Troubleshooting

loading

Table of Contents