Daikin VRV IV+ Installer And User Reference Manual page 124

Table of Contents

Advertisement

12
|
Technical data
Installer and user reference guide
124
Layout
2
a≥10 mm
b≥300 mm
c≥10 mm
d≥500 mm
e≥20 mm
3
a≥10 mm
b≥300 mm
c≥10 mm
d≥500 mm
e≥20 mm
f≥600 mm
4
a≥10 mm
b≥300 mm
c≥10 mm
d≥500 mm
e≥20 mm
5
a≥10 mm
b≥500 mm
c≥10 mm
d≥500 mm
e≥20 mm
f≥900 mm
h
2
F
d
(mm)
ABCD Sides along the installation site with obstacles
F Front side
Suction side
In case of an installation site where sides A+B+C+D have obstacles, the wall
heights of sides A+C have no impact on service space dimensions. Refer to the
figure above for impact of wall heights of sides B+D on service space dimensions.
In case of an installation site where only the sides A+B have obstacles, the wall
heights have no influence on any indicated service space dimensions.
The installation space required on these drawings are for full load heating
operation without considering possible ice accumulation. If the location of the
installation is in a cold climate, then all dimensions above should be >500 mm to
avoid accumulation of ice in between the outdoor units.
INFORMATION
The service space dimensions in above figure are based on cooling operation at 35°C
ambient temperature (standard conditions).
A+B+C+D
Possibility 1
Possibility 2
a≥50 mm
b≥100 mm
c≥50 mm
d≥500 mm
e≥100 mm
a≥50 mm
b≥100 mm
c≥50 mm
d≥500 mm
e≥100 mm
f≥500 mm
a≥50 mm
b≥100 mm
c≥50 mm
d≥500 mm
e≥100 mm
a≥50 mm
b≥500 mm
c≥50 mm
d≥500 mm
e≥100 mm
f≥600 mm
h
1
b
A+B
a≥200 mm
b≥300 mm
e≥400 mm
RYYQ+RYMQ+RXYQ8~20U7Y1B
VRV IV+ heat pump
4P546228-1A – 2019.10