Daikin VRV IV+ Installer And User Reference Manual page 38

Table of Contents

Advertisement

5
|
Preparation
Installer and user reference guide
38
Maximum allowable height difference
H1
≤50 m (40 m) (if outdoor is located below indoor units)
Conditional extension up till 90 m is possible without additional option
kit:
In case the outdoor location is higher than indoor: extension is possible
up till 90 m and following 2 conditions must be fulfilled:
-
Liquid piping size up (see table "Size up" in
refrigerant branch kit and indoor
-
Dedicated setting on outdoor unit is required (see [2‑49] in
"7.2.8 Mode 2: Field
In case the outdoor location is lower than indoor: extension is possible
up till 90 m and following 6 conditions must be fulfilled:
-
40~60 m: minimum connection ratio connected: 80%.
-
60~65 m: minimum connection ratio connected: 90%.
-
65~80 m: minimum connection ratio connected: 100%.
-
80~90 m: minimum connection ratio connected: 110%.
-
Liquid piping size up (see table "Size up" in
refrigerant branch kit and indoor
-
Dedicated setting on outdoor unit is required (see [2‑35] in
"7.2.8 Mode 2: Field
H2
≤30 m
H3
≤5 m
Maximum allowable length after branch
The pipe length from the first refrigerant branch kit to the indoor unit ≤40 m.
Example 1.1: unit 8: b+c+d+e+f+g+p≤40 m
Example 1.2: unit 6: b+h≤40 m, unit 8: i+k≤40 m
Example 1.3: unit 8: i≤40 m
However, extension is possible if all below conditions are met. In this case
limitation can be extended up to 90 m.
1
a
b
c
d
2
A
B
C
h
i
j
3
1
2
3
1 Outdoor units
2 Refnet joints (A~G)
3 Indoor unit (1~8)
Conditions:
a
The piping length between all indoor units to the nearest branch kit is ≤40 m.
Example: h, i, j ... p≤40 m
unit" [
4
settings" [
 92]).
unit" [
4
settings" [
 92]).
e
f
g
D
E
F
G
p
H1
k
l
m
n
4
5
6
7
8
H2
"E: Piping between
4
 32]).
"E: Piping between
4
 32]).
RYYQ+RYMQ+RXYQ8~20U7Y1B
VRV IV+ heat pump
4P546228-1A – 2019.10