CKM-CE75-E1M
24-10707-112 Rev. D
C
S
ONNECTING TO
For additional standby power wiring information, refer to the manufacturer's
documentation for Listed model EB-80 battery enclosure.
For UL 294 and UL 1076 installations, the CKM-CE75-E1M is intended to be
used with model EB-80 battery box and one 12VDC, 40Ah sealed lead acid
battery for standby power.
Note: Not all components are shown. Components are
not to scale. Refer to the Battery Disconnect Module
installation instructions for connection information.
Use Listed 14AWG stranded wire to connect the battery to the
CKM-CE75-E1M power supply.
Battery
Positive (+) terminal
Negative (-) terminal
P
TANDBY
OWER
EB-80
Battery
+
BLK
To
BDM
RED
Figure 3-4: Connecting to Standby Power
BDM
Red wire
Black wire
BAT+
BAT-
Orange wire
3-4
CKM-CE75-E1M
Battery
Disconnect
Module (BDM)
To
Batteries
CKM-FPO75
Power Supply
BAT+
BAT-
DC1+
Installation and Wiring