Cyclic Communication - Siemens SINAMICS G120 CU230P-2 HVAC Operating Instructions Manual

Frequency converters with the control units
Hide thumbs Also See for SINAMICS G120 CU230P-2 HVAC:
Table of Contents

Advertisement

6.1.4

Cyclic communication

The PROFIdrive profile defines different telegram types. Telegrams contain the data for
cyclic communication with a defined meaning and sequence. The inverter has the telegram
types listed in the table below.
Table 6- 3
Inverter telegram types
Telegram type (p0922)
Telegram 1
Speed control
PZD 2/2
Telegram 20
Speed control, VIK/NAMUR
PZD 2/6
Telegram 350
Speed control
PZD 4/4
Telegram 352
Speed control, PCS7
PZD 6/6
Telegram 353
Speed control,
PKW 4/4 and PZD 2/2
Telegram 354
Speed control,
PKW 4/4 and PZD 6/6
Telegram 999
Free interconnection via BICO
PZD n/m (n,m = 1 ... 8)
Table 6- 4
Explanation of the abbreviations
Abbreviation
Significance
STW1/2
Control word 1/2
ZSW1/2
Status word 1/2
NSOLL_A
Speed setpoint
NIST_A_GLATT
Smoothed speed actual value
IAIST_GLATT
Smoothed actual current value
MIST_GLATT
Actual torque
Frequency inverters with Control Units CU230P-2 HVAC, CU230P-2 DP, CU230P-2 CAN
Operating Instructions, 01/2011, FW 4.4, A5E02430659B AD
Process data (PZD) - control and status words, setpoints and actual values
PZD01
PZD02
PZD03
STW1
HSW
ZSW1
HIW
STW1
NSOLL_A
⇐ The inverter receives this data from the control
ZSW1
NIST_A
⇒ The inverter sends this data to the control
STW1
NSOLL_A
ZSW1
NIST_A_
IAIST_
GLATT
GLATT
STW1
NSOLL_A
M_LIM
ZSW1
NIST_A_
IAIST_
GLATT
GLATT
STW1
NSOLL_A
ZSW1
NIST_A_
IAIST_
GLATT
GLATT
STW1
NSOLL_A
ZSW1
NIST_A_
GLATT
STW1
NSOLL_A
ZSW1
NIST_A_
IAIST_
GLATT
GLATT
STW1
Telegram length on receipt can be configured up to max. 8 words
ZSW1
Telegram length on transmission can be configured up to max. 8 words
6.1 Communication via PROFIBUS
PZD04
PZD05
MIST_
PIST_
GLATT
GLATT
STW3
ZSW3
PCS7 process data
MIST_
WARN_
GLATT
CODE
PCS7 process data
MIST_
WARN_
GLATT
CODE
Abbreviation
Significance
PIST_GLATT
Actual active power
MELD_NAMUR
Control word according to the VIK-
NAMUR definition
M_LIM
Torque limit value
FAULT_CODE
Fault number
WARN_CODE
Alarm number
Configuring the fieldbus
PZD06
PZD07
PZD08
MELD_
NAMUR
FAULT_
CODE
FAULT_
CODE
101