Technical data

NOTICE
UL-certified fuses must be used
In order that the system is in compliance with UL, UL certified fuses, circuit breakers or self-
protected combination motor controllers must be used.
10.1

Technical data for CU230P-2

Table 10- 1
General technical data of the CU230P-2
Feature
Order numbers
Operating voltage
Power loss
Output voltages
Setpoint resolution
Fixed speeds
Skip speeds
Digital inputs
Analog inputs
Digital outputs / relay
outputs
Analog outputs
Frequency inverters with Control Units CU230P-2 HVAC, CU230P-2 DP, CU230P-2 CAN
Operating Instructions, 01/2011, FW 4.4, A5E02430659B AD
Data / explanation
6SL3243-0BB30-1CA2:
6SL3243-0BB30-1HA2:
6SL3243-0BB30-1PA2:
20.4 V DC ... 28.8 V, 1 A
5.0 W
18 V ... 30 V (max. 200 mA)
18 V ... 30 V (max. 200 mA)
10 V ± 0.5 V (max. 10 mA)
0.01 Hz
16
4
6 (DI0 ... DI5)
4 (AI0 ... AI3)
3 (DO0 ... DO2)
2 (AO0 ... AO1)
with CANopen interface
with RS485 interface for communication via USS protocol,
BacNet MS/TP and Modbus RTU
with PROFIBUS interface
Supply from the Power Module or external via terminals 31 and
32
plus power loss of the output voltages
Adjustable
Adjustable
Low < 5 V, High > 11 V, maximum input voltage 30 V, current
consumption 5.5 mA, isolated; SIMATIC compatible, PNP/NPN
switchable, reaction time: 10 ms without debounce time (p0724)
Differential inputs, 12 bit resolution,
switchable: Current (0 mA ... 20 mA) / voltage (0 V ... 10 V, -
10 V ... + 10 V) / temperature,
response time: 13 ms without debounce time (p0724), AI0 and
AI1 configurable as additional digital inputs: Low < 1.6 V,
High > 4.0 V
DO0 ... DO2: 30 V DC 5 A
DO1 additional: 230 V AC, 2 A
update time: 2 ms
0 V ... 10 V / 0 mA ... 20 mA, update time: 4 ms