Dimensions, Hole Drilling Templates, Minimum Clearances, Tightening Torques - Siemens SINAMICS G120 CU230P-2 HVAC Operating Instructions Manual

Frequency converters with the control units
Hide thumbs Also See for SINAMICS G120 CU230P-2 HVAC:
Table of Contents

Advertisement

3.3.1

Dimensions, hole drilling templates, minimum clearances, tightening torques

Note
For Power Modules up to 132 kW, degree of protection IP20, the CU230P-2 increases the
total inverter depth by 50 mm - and an additional 30 mm if you use an IOP.
Dimensions and drilling patterns for the PM230 Power Modules
Figure 3-1
Table 3- 1
Dimensions for PM230, IP55
Frame size
FSA
FSB
FSC
FSD
FSE
FSF
Fixing:
Frequency inverters with Control Units CU230P-2 HVAC, CU230P-2 DP, CU230P-2 CAN
Operating Instructions, 01/2011, FW 4.4, A5E02430659B AD
Drilling pattern for PM230
Dimensions (mm)
Height
Width
460
154
540
180
620
230
640
320
751
320
915
410
FSA/FSB: screws M4, 2.5 Nm,
FSC: screws M5, 2.5 Nm,
Depth
a
238
445
238
524
238
604
238
600
238
710
238
870
FSD/FSE/FSF: screws M8, 13 Nm
3.3 Installing Power Module
Clearances (mm)
b
c
132
100
158
100
208
125
285
300
285
300
370
300
Installing
d
0
0
0
0
0
0
31

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g120 cu230p-2 dpSinamics g120 cu230p-2 can

Table of Contents