EDUS281120_a
CAUTION
• Install the indoor and outdoor units, power supply wiring and
connecting wires at least 3.3 ft away from televisions or radios
in order to prevent image interference or noise.
(Depending on the radio waves, a distance of 3.3 ft may not
be sufficient enough to eliminate the noise.)
• In the case of the installation of a wireless remote controller, the
transmission distance of the wireless remote controller may be
shortened if the room has a fluorescent light of electronic light-
ing type (i.e., an inverter or rapid-start fluorescent light).
Keep the distance between the receiver and the fluorescent
light as far as possible.
(2) Use suspension bolts to install the indoor unit. Check that
the place of installation withstands the weight of the indoor
unit. Secure the suspension bolts with proper beams if nec-
essary.
Ceiling
• The H1 dimension indicates the
height of the product.
• Determine the H2 dimension by
maintaining a downward slope of
at least 1/100 as specified in
"7. DRAIN PIPING WORK".
4.
PREPARATIONS BEFORE INSTALLATION
(1) Check the positional relationship between the ceiling open-
ing hole and the suspension bolt of the unit.
• For the maintenance, inspection, and other servicing
purposes of the control box and drain pump, prepare one
of the following service spaces.
1. Inspection hatch 1 (17-3/4 × 17-3/4) for the control
box and a minimum space of 12 in. for the lower part
of the product. (Refer to Fig. 2-2)
2. Inspection hatch 1 (17-3/4 × 17-3/4) for the control
box and inspection hatch 2 for the lower part of the
product (see arrow view A-1). (Refer to Fig. 2-3)
3. Inspection hatch 3 for the lower part of the product
and the lower part of the control box (see arrow view
A-2). (Refer to Fig. 2-3)
English
RZR-P, RZQ-P(9)
(length: in.)
Floor surface
Min. 28 (service space)
[Required installation place]
The dimensions indicate the
minimum required space of
installation.
Fig. 2-1
Case 1
Inspection hatch
28
24-13/16
(Suspension bolt pitch)
Air outlet
Bottom of unit
Suspension bolt (× 4)
Case 2, 3
Inspection hatch
(Ceiling opening)
Inspection hatch
A
Inspection hatch 1
(17-3/4×17-3/4)
Control box
Inspection
hatch 2
28
(Same as the
indoor unit
size or more)
Arrow view A-1
• Determine the H3
dimension by maintaining a
18 • 24 • 30 type
downward slope of at least
36 • 42 type
1/100 as specified in
"7. DRAIN PIPING WORK".
Installation of indoor unit
(length: in.)
Control box
Ceiling
Inspection hatch 1
(17-3/4×17-3/4)
Control box
Air inlet
Fig. 2-2
Control box
Ceiling
Inspection hatch 3
(Same as the indoor
unit size +12 or more)
Control box
28
Arow view A-2
Fig. 2-3
Model
B
C
D
40 40-7/8 52
56 56-5/8 68
(length: in.)
5
3PN14093-12A
191