Daikin SkyAir RZR-P Series Engineering Data page 169

Cooling only 60hz, heat pump 60hz, r-410a, inverter
Hide thumbs Also See for SkyAir RZR-P Series:
Table of Contents

Advertisement

Installation of indoor unit
(b) where corrosive gas, such as sulfurous acid gas, is produced. Corroding copper pipes or soldered
parts may result in refrigerant leakage.
(c) near machinery emitting electromagnetic waves. Electromagnetic waves may disturb the operation of
the control system and result in a malfunction of the equipment.
(d) where fl ammable gases may leak, where there are carbon fi ber or ignitable dust suspensions in the
air, or where volatile liquids such as thinner or gasoline are handled.
Operating the unit in such conditions may result in fi re.
Heat exchanger fi ns are sharp enough to cut.
To avoid injury wear gloves to cover the fi ns when working around them.
Refrigerant pipes may be very hot or very cold during or immediately after operation.
Touching them could result in burns or frostbite. To avoid injury give the pipes time to return to normal
temperature or, if you must touch them, be sure to wear proper gloves.
CAUTION
While following the instructions in this installation manual, insulate piping in order to prevent con-
densation.
Improper piping insulation may result in water leakage and property damage.
Be very careful about product transportation.
Some products use PP bands for packaging. Do not use any PP bands for a means of transportation. It
is dangerous.
Do not turn off the power immediately after stopping operation.
Always wait at least fi ve minutes before turning off the power. Otherwise, water leakage and trouble may occur.
Make sure to provide for adequate measures in order to prevent that the outdoor unit be used as a
shelter by small animals.
Small animals making contact with electrical parts can cause malfunctions, smoke or fi re. Please instruct
the customer to keep the area around the unit clean.
NOTE
Install the indoor and outdoor units, power supply wiring and connecting wires at least 3.5ft. away
from televisions or radios in order to prevent image interference or noise.
(Depending on the radio waves, a distance of 3.5ft. may not be suffi cient enough to eliminate the noise.)
Remote controller (wireless kit) transmitting distance can result shorter than expected in rooms
with electronic fl uorescent lamps. (inverter or rapid start types)
Install the indoor unit as far away from fl uorescent lamps as possible.
Dismantling of the unit, treatment of the refrigerant, oil and eventual other parts, should be done in
accordance with the relevant local and national regulations.
2.
BEFORE INSTALLATION
When moving the unit while removing it from the packing case, be sure to lift it by the four hanger
brackets. Avoid putting any pressure on other parts, especially, horizontal flaps, the refrigerant pip-
ing, drain piping, and other resin parts.
Be sure to remove a cushion (corrugated paper) located between the heat exchanger and the right air fi lter.
Be sure to check the type of R410A refrigerant to be used before installing the unit. (Using an incorrect
refrigerant will prevent normal operation of the unit.)
The accessories needed for installation must be retained in your custody until the installation work is
completed. Do not discard them!
Decide upon a line of transport.
Leave the unit inside its packaging while moving, until reaching the installation site. Where unpacking is
unavoidable, use a sling of soft material or protective plates together with a rope when lifting, to avoid
damage or scratches to the unit.
3
168
EDUS281120_a
English
C: 3PN07521-2C
RZR-P, RZQ-P(9)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents