Daikin SkyAir RZR-P Series Engineering Data page 12

Cooling only 60hz, heat pump 60hz, r-410a, inverter
Hide thumbs Also See for SkyAir RZR-P Series:
Table of Contents

Advertisement

EDUS281120_a
3.1.3
FAQ
Wall mounted type
Indoor unit
Model
Outdoor unit
Power supply
1, 2
Cooling capacity
SEER (Rated)
EER (Rated)
Indoor unit
Color
Dimensions
H×W×D
Type
Coil
Rows×Stages×FPI
Face area
Model
Type
Fan
Motor output
Airflow rate (H/L)
Air filter
Mass (Weight)
Liquid
Piping
Gas
connections
Drain
Wired
Remote controller (option)
Wireless
Outdoor unit
Color
Dimensions
H×W×D
Type
Coil
Rows×Stages×FPI
Face area
Model
Comp.
Type
Motor output
Model
Type
Fan
Motor output
Airflow rate
Mass (Weight)
Liquid
Piping
Gas
connections
Drain
Safety devices
Capacity step
Refrigerant control
Standard length
Ref. piping
Max. length
Max. height difference
Model
Refrigerant
Charge (factory charge)
Ref. oil
Drawing Number
Notes:
1. Indoor temp. : 80°FDB, 67°FWB (27°CDB /19.4°CWB) / outdoor temp. : 95°FDB (35°CDB) / Equivalent piping length : 25 ft (7.5 m), level difference : 0.
2. Capacities are net, including a deduction for cooling for indoor fan motor heat.
RZR-P, RZQ-P(9)
1 phase, 208/230V, 60Hz
Btu/h
Btu/h-W
White (3.0Y8.5/0.5)
in (mm)
11–3/8 × 41–3/8 × 9 (289 x 1051 x 229)
ft² (m²)
W
3
cfm (m
/min)
Resin net (Washable)
Lbs (kg)
3/8 (9.5) (Flare connection)
in (mm)
5/8 (15.8) (Flare connection)
in (mm)
in (mm)
VP13 (External dia. 11/16 (17.5), Internal dia. 1/2 (12.7))
30–5/16 × 35–7/16 × 12–5/8
in (mm)
(770 x 900 x 321)
ft² (m²)
Hermetically sealed swing type
kW
W
3
cfm (m
/min)
Lbs (kg)
3/8 (9.5) (Flare connection)
in (mm)
5/8 (15.8) (Flare connection)
in (mm)
in (mm)
High pressure switch.
Outdoor fan driver overload protector.
Thermal protector for indoor fan motor.
Inverter overload protector.
Fusible plugs. Fuse.
%
Electronic expansion valve
ft (m)
ft (m)
ft (m)
Lbs (kg)
Refer to the name plate of compressor.
FAQ18PVJU
RZR18PVJU
18,000
18.6
12.7
FAQ18PVJU
Cross fin coil
2 × 14 × 18
2.29 (0.7)
QCL9686M
Cross flow fan
43
500/400 (14/11)
31 (14)
BRC1E71
BRC7E818
RZR18PVJU
Ivory
Cross fin coil
2 × 34 × 18
7.1 (2.2)
2YC63HXD#ED
1.7
P47N11F
Propeller fan
70
1,835 (52)
150 (68)
1 (25.4) (Hole)
35-100
25 (7.5)
164 (50)
98 (30)
R-410A
5.1 (2.3)
C: 4D071677
Specifications
FAQ24PVJU
RZR24PVJU
1 phase, 208/230V, 60Hz
24,000
17.6
10.2
FAQ24PVJU
White (3.0Y8.5/0.5)
11–3/8 × 41–3/8 × 9 (289 x 1051 x 229)
Cross fin coil
2 × 14 × 18
2.29 (0.7)
QCL9686M
Cross flow fan
43
635/470 (18/13)
Resin net (Washable)
31 (14)
3/8 (9.5)(Flare connection)
5/8 (15.8)(Flare connection)
VP13 (External dia. 11/16 (17.5), Internal dia. 1/2 (12.7))
BRC1E71
BRC7E818
RZR24PVJU
Ivory
30–5/16 × 35–7/16 × 12–5/8
(770 x 900 x 321)
Cross fin coil
2 × 34 × 18
7.1 (2.2)
2YC63HXD#ED
Hermetically sealed swing type
1.7
P47N11F
Propeller fan
70
1,835 (52)
150 (68)
3/8 (9.5) (Flare connection)
5/8 (15.8) (Flare connection)
1 (25.4) (Hole)
High pressure switch.
Outdoor fan driver overload protector.
Thermal protector for indoor fan motor.
Inverter overload protector.
Fusible plugs. Fuse.
30-100
Electronic expansion valve
25 (7.5)
164 (50)
98 (30)
R-410A
5.1 (2.3)
Refer to the name plate of compressor.
C: 4D071677
11

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents