Routine Maintenance - Carrier WeatherMaster Puron 48HC D17 Service And Maintenance Instructions

Gas heat/electric cooling with r-410a refrigerant
Table of Contents

Advertisement

OUTDOOR AIR
HOOD
DISCONNECT
CONVENIENCE
OUTLET
CONTROL BOX
ACCESS PANEL
ACCESS PANEL
Fig. 1 — Access Panels and Components (Front)
CONDENSER COIL
CIRCUIT A
CONDENSER COIL
CIRCUIT B
Fig. 2 — Typical Access Panel Location (Rear)

Routine Maintenance

These items should be part of a routine maintenance program,
to be checked every month or two, until a specific schedule for
each can be identified for this installation.
QUARTERLY INSPECTION (AND 30 DAYS AFTER INI-
TIAL START)
The 48HC units should be inspected and serviced every three
months.
Return air filter replacement
Outdoor hood inlet filters cleaned
Belt tension checked
Belt condition checked
Pulley alignment checked
Fan shaft bearing locking collar tightness checked
Condenser coil cleanliness checked
Condensate drain checked
SEASONAL MAINTENANCE
These items should be checked at the beginning of each season
(or more often if local conditions and usage patterns dictate).
Air Conditioning
Condenser fan motor mounting bolts tightness
Compressor mounting bolts
Condenser fan blade positioning
Control box cleanliness and wiring condition
Wire terminal tightness
SUPPLY FAN
OUTDOOR
HEATING SECTION
FANS/MOTORS
RETURN AIR
COMPRESSOR
FILTER AND
GAS SECTION
(CIRCUIT A)
INDOOR COIL
ACCESS PANEL
COMPRESSOR
CIRCUIT B
Refrigerant charge level
Evaporator coil cleaning
Evaporator blower motor amperage
Heating
Heat exchanger flue passageways cleanliness
Gas burner condition
Gas manifold pressure
Heating temperature rise
Economizer or Outside Air Damper
CONDENSER
Inlet filters condition
COIL
(CIRCUIT A)
Check damper travel (economizer)
Check gear and dampers for debris and dirt
Air Filters and Screens
Each unit is equipped with return air filters. If the unit has an
economizer, it will also have an outside air screen. If a manual
outside air damper is added, an inlet air screen will also be
present.
Each of these filters and screens will need to be periodically re-
placed or cleaned.
Return Air Filters
Return air filters are disposable fiberglass media type. Access
to the filters is through the vertical panel to the right of the con-
trol box. Filters are situated on slide-out racks for easy inspec-
tion and repair. See Fig. 1.
EQUIPMENT DAMAGE HAZARD
Failure to follow this CAUTION can result in premature
wear and damage to equipment.
DO NOT OPERATE THE UNIT WITHOUT THE RE-
TURN AIR FILTERS IN PLACE.
Dirt and debris can collect on heat exchangers and coils
possibly resulting in a small fire. Dirt buildup on compo-
nents can cause excessive current used resulting in motor
failure.
Removing the Return Air Filters
1.
Remove the Return Air Filter and Indoor Coil Access
Panel. See Fig. 1.
2.
Reach inside and remove the filters from the filter rack.
3.
Replace the filters, as required, with similar replacement
filters of the same size.
4.
Re-install the Return Air Filter and Indoor Coil Access
Panel.
Outdoor Air Hood
The outdoor air hood inlet screens are permanent aluminum-
mesh type filters. See Fig. 2. Inspect these screens for cleanli-
ness. Remove the screens when cleaning is required. Clean by
washing with hot low-pressure water and soft detergent. Re-
place all screens before restarting the unit. Observe the flow di-
rection arrows on the side of each screen frame.
Economizer Inlet Air Screen
The inlet air screen is retained by filter clips under the top edge
of the hood. See Fig. 3.
Remove screens by removing the screws in the horizontal clips
on the leading edge of the hood. Slide filters out. See Fig. 3.
Install filters, by sliding clean or new filters into the hood side
retainers. Once positioned, re-install the horizontal clips.
3
CAUTION

Advertisement

Table of Contents
loading

Table of Contents