Economi$Er Systems - Carrier WeatherMaster Puron 48HC D17 Service And Maintenance Instructions

Gas heat/electric cooling with r-410a refrigerant
Table of Contents

Advertisement

ECONOMI$ER SYSTEMS

IMPORTANT: Any economizer that meets the economizer
requirements as laid out in California's Title 24 mandatory
section 120.2 (fault detection and diagnostics) and/or pre-
scriptive section 140.4 (life-cycle tests, damper leakage,
5 year warranty, sensor accuracy, etc), will have a label on
the economizer. Any economizer without this label does
not meet California's Title 24. The five year limited parts
warranty referred to in section 140.4 only applies to fac-
tory-installed economizers. Please refer to the economizer
on the unit.
The 48HC units may be equipped with a factory-installed or
accessory (field-installed) EconoMi$er system. Three types are
available: with a logic control system (EconoMi$er IV and
EconoMi$er X) and without a control system (EconoMi$er2).
See Fig. 54-56 for component locations on each type. The
W7212 controller is used for EconoMi$er IV and the W7220
controller is used for EconoMi$er X. See Fig. 57-60 for
EconoMi$er section wiring diagrams.
All three EconoMi$ers use direct-drive damper actuators.
WIRING
HARNESS
ACTUATOR
Fig. 54 — EconoMi$er IV Component Locations
ECONOMI$ER IV
CONTROLLER
OUTSIDE AIR
TEMPERATURE SENSOR
LOW AMBIENT
SENSOR
Fig. 55 — EconoMi$er X Component Locations
ECONOMI$ER2
PLUG
BAROMETRIC
RELIEF
DAMPER
Fig. 56 — EconoMi$er 2 Component Locations
45
WIRING HARNESS
OUTSIDE AIR
TEMPERATURE SENSOR
OUTDOOR
AIR HOOD
GEAR DRIVEN
DAMPER
HOOD
SHIPPING
BRACKET