Carrier WeatherMaster Puron 48HC D17 Service And Maintenance Instructions page 65

Gas heat/electric cooling with r-410a refrigerant
Table of Contents

Advertisement

Table 33 — Dry Bulb Operation with DCV (CO
DEMAND
OUTSIDE AIR
CONTROLLED
GOOD TO
VENTILATION (DCV)
ECONOMIZE
Below CO
Set
2
Above CO
Set
2
*With 2SP FAN DELAY (Advanced Setup Menu) when in the economizing mode there is a delay for the high speed fan to try to satisfy the call for sec-
ond stage cooling by turning on the fan to high and opening the OA damper 100% before the first stage mechanical cooling is enabled.
†With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on second stage of mechanical cooling Y2–O after the delay if the call for Y1–I and
Y2–I have not been satisfied.
Table 34 — Enthalpy Operation without DCV (CO
DEMAND
OUTSIDE AIR
CONTROLLED
GOOD TO
VENTILATION (DCV)
ECONOMIZE
NO CO
SENSOR
2
*With 2SP FAN DELAY (Advanced Setup Menu) when in the economizing mode there is a delay for the high speed fan to try to satisfy the call for second
stage cooling by turning on the fan to high and opening the OA damper 100% before the first stage mechanical cooling is enabled.
†With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on second stage of mechanical cooling Y2–O after the delay if the call for Y1–I and
Y2–I have not been satisfied.
Y1-I
Y2-I
OFF
OFF
No
ON
OFF
ON
ON
OFF
OFF
ON
OFF
Yes
ON
ON
OFF
OFF
No
ON
OFF
ON
ON
OFF
OFF
Yes
ON
OFF
ON
ON
Y1-I
Y2-I
OFF
OFF
NO
ON
OFF
ON
ON
OFF
OFF
ON
OFF
YES
ON
ON
Sensor) — 2 Speed Fan
2
FAN
Y1-O
Y2-O
SPEED
LOW
0v/Off
0v/Off
LOW
24v/On
0v/Off
HIGH
24v/On
24v/On
LOW
0v/Off
0v/Off
LOW
0v/Off
0v/Off
HIGH
24v/On
0v/Off
LOW
0v/Off
0v/Off
LOW
24v/On
0v/Off
HIGH
24v/On
24v/On
LOW
0v/Off
0v/Off
LOW
0v/Off
0v/Off
DELAY*
HIGH
0v/Off†
24v/On
Sensor) — 2 Speed Fan
2
FAN
Y1-O
Y2-O
SPEED
LOW
0v/Off
0v/Off
LOW
24v/On
0v/Off
HIGH
24v/On
24v/On
LOW
0v/Off
0v/Off
LOW
0v/Off
0v/Off
DELAY*
HIGH
0v/Off†
24v/On
65
OCCUPIED
UNOCCUPIED
VENTMIN
VENTMIN
VENTMIN
VENTMIN
VENTMIN to
Closed to Full-Open
Full-Open
VENTMIN to
Closed to Full-Open
Full-Open
VENTMIN to
VENTMAX
VENTMIN to
VENTMAX
VENTMIN to
VENTMAX
VENTMIN to
VENTMAX
VENTMIN to
Closed to Full-Open
Full-Open
VENTMIN to
Closed to Full-Open
Full-Open
OCCUPIED
UNOCCUPIED
MIN POS
MIN POS
MIN POS
MIN POS
MIN POS to Full Open
Closed to Full-Open
MIN POS to Full Open
Closed to Full-Open
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed