Carrier WeatherMaster Puron 48HC D17 Service And Maintenance Instructions page 57

Gas heat/electric cooling with r-410a refrigerant
Table of Contents

Advertisement

Table 24 — HH57AC081 Sensor Wiring Terminations
TERMINAL
NUMBER
LABEL
1
S-BUS
2
S-BUS
Use Fig. 72 and Table 25 to set the DIP switches for the desired
use of the sensor.
Table 25 — HH57AC081 Sensor DIP Switch
DIP SWITCH POSITIONS FOR SWITCHES 1, 2, AND 3
USE
1
DA
OFF
RA
ON
OA
OFF
NOTE: When an S-Bus sensor is connected to an existing net-
work, it will take 60 minutes for the network to recognize and
auto-configure itself to use the new sensor.
During the 60-minute setup period, no alarms for sensor fail-
ures (except SAT) will be issued and no economizing function
will be available.
CO
Sensor Wiring
2
When using a CO
sensor, the black and brown common wires
2
are internally connected and only one is connected to "IAQ
COM" on the W7220. Use the power from the W7220 to pow-
er the CO
sensor OR make sure the ground for the power sup-
2
plies are common. See Fig. 73 for CO
CO
SENSOR
2
24V
+
ANALOG
OUT
1
POWER SUPPLY. PROVIDE DISCONNECT
MEANS AND OVERLOAD PROTECTION
AS REQUIRED.
Fig. 73 — CO
INTERFACE OVERVIEW
This section describes how to use the EconoMi$er
face for:
Keypad and menu navigation
Settings and parameter changes
Menu structure and selection
User Interface
The user interface consists of a 2-line LCD display and a 4-button
keypad on the front of the economizer controller.
Keypad
Use the four navigation buttons (see Fig. 74) to scroll through
the menus and menu items, select menu items, and to change
parameter and configuration settings.
To use the keypad when working with menus:
TYPE
DESCRIPTION
S-BUS
Communications
S-BUS
(Enthalpy Control
Sensor Bus)
S-BUS
Communications
S-BUS
(Enthalpy Control
Sensor Bus)
2
3
ON
OFF
OFF
OFF
OFF
OFF
sensor wiring.
2
RED
L1
(HOT)
BLACK
L2
1
YELLOW
BROWN
ORANGE
GREEN
Sensor Wiring
2
®
user inter-
Press the ▲ (Up arrow) button to move to the previous
menu.
Press the ▼ (Down arrow) button to move to the next
menu.
Press the
(Enter) button to display the first item in the
currently displayed menu.
Press the
(Menu Up/Exit) button to exit a menu's item
and return to the list of menus.
Fig. 74 — W7220 Controller Navigation Buttons
To use the keypad when working with Setpoints, System and
Advanced Settings, Checkout tests and Alarms:
1.
Navigate to the desired menu.
2.
Press the
(Enter) button to display the first item in the
currently displayed menu.
3.
Use the ▲ and ▼ buttons to scroll to the desired
parameter.
4.
Press the
(Enter) button to display the value of the
currently displayed item.
5.
Press the ▲ button to increase (change) the displayed
parameter value.
6.
Press the ▼ button to decrease (change) the displayed
parameter value.
NOTE: When values are displayed, pressing and holding the
▲ or ▼ button causes the display to automatically increment or
decrement.
1.
Press the
(Enter) button to accept the displayed value
and store it in nonvolatile RAM. "CHANGE STORED"
displays.
2.
Press the
(Enter) button to return to the current menu
parameter.
3.
Press the
(Menu Up/Exit) button to return to the previ-
ous menu.
Menu Structure
Table 26 illustrates the complete hierarchy of menus and parame-
ters for the EconoMi$er
®
The Menus in display order are:
STATUS
SETPOINTS
SYSTEM SETUP
ADVANCED SETUP
CHECKOUT
ALARMS
NOTE: Some parameters in the menus use the letters MA or
MAT, indicating a mixed air temperature sensor location before
the cooling coil. This unit application has the control sensor
57
X system.