Unit Arrangement And Access; General; Routine Maintenance; Filters - Carrier 48JCH 04-06 Series Service And Maintenance Instructions

Single package rooftop ultra low nox (14 ng /j) gas heat / electric cooling unit with puron (r-410a) refrigerant 3 to 5 nominal tons
Table of Contents

Advertisement

UNIT ARRANGEMENT AND ACCESS

General

Figures 1 and 2 show general unit arrangement and access
locations.
Filter Access Panel
Fig. 1 — Typical Access Panel Locations
Fig. 2 — Blower Access Panel Location

Routine Maintenance

These items should be part of a routine maintenance program, to
be checked every month or two, until a specific schedule for each
can be identified for this installation:
QUARTERLY INSPECTION (AND 30 DAYS AFTER
INITIAL START)
Return air filter replacement
Outdoor hood inlet filters cleaned
Condenser coil cleanliness checked
Condensate drain checked
SEASONAL MAINTENANCE
These items should be checked at the beginning of each season (or
more often if local conditions and usage patterns dictate):
Air Conditioning
Ensure outdoor fan motor mounting bolts are tight
Ensure compressor mounting bolts are tight
Inspect outdoor fan blade positioning
Ensure control box is clean
Check control box wiring condition
Ensure wire terminals are tight
Check refrigerant charge level
Ensure indoor coils are clean
Check supply blower motor amperage
Compressor
Access Panel
Outdoor-Air Opening and
Indoor Coil Access Panel
Blower
Access
Panel
Heating
Heat exchanger flue passageways cleanliness
Gas burner condition
Gas manifold pressure
Heating temperature rise
Economizer or Outside Air Damper
Check inlet filters condition
Check damper travel (economizer)
Check gear and dampers for debris and dirt
Air Filters and Screens
Each unit is equipped with return air filters. If the unit has an econ-
omizer, it will also have an outside air screen. If a manual outside
air damper is added, an inlet air screen will also be present.
Each of these filters and screens will need to be periodically re-
placed or cleaned.

Filters

RETURN AIR FILTERS
EQUIPMENT DAMAGE HAZARD
Failure to follow this CAUTION can result in premature wear
and damage to equipment.
DO NOT OPERATE THE UNIT WITHOUT THE RETURN
AIR FILTERS IN PLACE.
Dirt and debris can collect on heat exchangers and coils
possibly resulting in a small fire. Dirt buildup on components
can cause excessive current used resulting in motor failure.
Return air filters are disposable fiberglass media type. Access to
the filters is through the small lift-out panel located on the rear
side of the unit, above the evaporator/return air access panel (see
Fig. 3).
To remove the filters:
1.
Grasp the bottom flange of the upper panel.
2.
Lift up and swing the bottom out until the panel disen-
gages and pulls out.
3.
Reach inside and extract the filters from the filter rack.
4.
Replace these filters as required with similar replacement
filters of same size.
To re-install the access panel:
1.
Slide the top of the panel up under the unit top panel.
2.
Slide the bottom into the side channels.
3.
Push the bottom flange down until it contacts the top of
the lower panel (or economizer top).
OUTSIDE AIR HOOD
Outside air hood inlet screens are permanent aluminum-mesh
type filters. Check these for cleanliness. Remove the screens
when cleaning is required. Clean by washing with hot low-pres-
sure water and soft detergent and replace all screens before re-
starting the unit. Observe the flow direction arrows on the side of
each filter frame.
ECONOMIZER INLET AIR SCREEN
This air screen is retained by filter clips under the top edge of the
hood (see Fig. 3).
3
CAUTION

Advertisement

Table of Contents
loading

This manual is also suitable for:

48jcg 04-06 series

Table of Contents