* As the height above sea level increases, there is less oxygen per cubic ft. of air. Therefore, heat input rate should be reduced at higher altitudes.
KIT NO.:
XX
1
= CRNGELEV001A00
XX
2
= CRNGELEV002A00
XX
3
= CRLPELEV005A00
XX
4
= CRLPELEV006A00
XX
= CRLPKIT9001A00
5
PROPANE GAS
ELEVATION
Feet
Meters
0-2000
0-610
2000
610
3000
914
4000
1219
5000
1524
6000
1829
7000
2134
8000
2438
9000
2743
10,000
3048
11,000
3353
12,000
3658
13,000
3962
14,000
4267
* As the height above sea level increases, there is less oxygen per cubic ft. of air. Therefore, heat input rate should be reduced at higher altitudes.
KIT NO.:
XX
= CRNGELEV001A00
1
XX
2
= CRNGELEV002A00
XX
3
= CRLPELEV005A00
XX
4
= CRLPELEV006A00
XX
5
= CRLPKIT9001A00
Table 16 — Altitude Compensation* (17-30) for Natural Gas
220k BTUH
Orifice Size
Input (btu/hr)
30
220,000
30
202,400
31
193,600
1
31
184,800
1
31
1
176,000
31
1
167,200
32
1
158,400
32
1
149,600
34
1
140,800
35
132,000
2
37
2
123,200
37
2
114,400
39
2
105,600
39
2
96,800
Table 17 — Altitude Compensation* (17-30) for Propane Gas