Carrier WeatherMaster Puron 48HC D17 Service And Maintenance Instructions page 23

Gas heat/electric cooling with r-410a refrigerant
Table of Contents

Advertisement

PROBLEM
Compressor and Condenser Fan Will
Not Start.
Compressor Will Not Start But
Condenser Fan Runs.
Compressor Cycles (other than
normally satisfying thermostat).
Compressor Operates Continuously.
Excessive Head Pressure.
Head Pressure Too Low.
Excessive Suction Pressure.
Suction Pressure Too Low.
Evaporator Fan Will Not Shut Off.
Compressor Makes Excessive Noise. Compressor rotating in wrong direction.
Table 5 — Cooling Service Troubleshooting
CAUSE
Power failure.
Fuse blown or circuit breaker tripped.
Defective thermostat, contactor, transformer,
or control relay.
Insufficient line voltage.
Incorrect or faulty wiring.
Thermostat setting too high.
Faulty wiring or loose connections in
compressor circuit.
Compressor motor burned out, seized, or
internal overload open.
Defective run/start capacitor, overload, start
relay.
One leg of three-phase power dead.
Refrigerant overcharge or undercharge.
Defective compressor.
Insufficient line voltage.
Blocked condenser.
Defective run/start capacitor, overload, or start
relay.
Defective thermostat.
Faulty condenser-fan motor or capacitor.
Restriction in refrigerant system.
Dirty air filter.
Unit undersized for load.
Thermostat set too low.
Low refrigerant charge.
Leaking valves in compressor.
Air in system.
Condenser coil dirty or restricted.
Dirty air filter.
Dirty condenser coil.
Refrigerant overcharged.
Faulty TXV valve.
Condenser air restricted or air short-cycling.
Low refrigerant charge.
Compressor valves leaking.
Restriction in liquid tube.
High head load.
Compressor valves leaking.
Refrigerant overcharged.
Dirty air filter.
Low refrigerant charge.
Faulty TXV valve.
Insufficient evaporator airflow.
Temperature too low in conditioned area.
Outdoor ambient below 25°F.
Time off delay not finished.
23
REMEDY
Call power company.
Replace fuse or reset circuit breaker.
Replace defective component.
Determine cause and correct.
Check wiring diagram and rewire correctly.
Lower thermostat setting below room temperature.
Check wiring and repair or replace. Tighten loose
connections.
Determine cause. Replace compressor.
Determine cause and replace defective component.
Replace fuse or reset circuit breaker. Determine cause.
Recover refrigerant, evacuate system, and recharge to to
values on nameplate.
Replace defective compressor.
Determine cause and correct.
Determine cause and correct.
Determine cause and replace.
Replace thermostat.
Replace defective fan motor or capacitor.
Locate restriction and remove.
Replace air filter.
Decrease load or replace with larger unit.
Reset thermostat.
Locate leak; repair and recharge.
Replace compressor.
Recover refrigerant, evacuate system, and recharge.
Clean coil or remove restriction.
Replace air filter.
Clean condenser coil.
Recover excess refrigerant.
1. Check TXV bulb mounting and secure tightly to suction
line and insulate.
2. Replace TXV valve and filter drier if stuck open or
closed.
Determine cause and correct.
Check for leaks; repair and recharge.
Replace compressor.
Remove restriction.
Check for source and eliminate.
Replace compressor.
Recover excess refrigerant.
Replace air filter.
Check for refrigerant leaks; repair and recharge.
1. Check TXV bulb mounting and secure tightly to suction
line and insulate.
2. Replace TXV valve and filter drier if stuck open or
closed.
Increase air quantity. Check filter and replace if
necessary. Check belt tension on blower.
Reset thermostat.
Install low-ambient kit.
Wait for 30-second off delay.
Reverse the 3-phase power leads.

Advertisement

Table of Contents
loading

Table of Contents