Carrier WeatherMaster Puron 48HC D17 Service And Maintenance Instructions page 41

Gas heat/electric cooling with r-410a refrigerant
Table of Contents

Advertisement

TERMINAL LABEL
INPUTS
RT, C
SS
FS, T1
W
RS
LS
CS
Centrifugal switch (not used)
OUTPUTS
L1, CM
IFO
GV
Fig. 52 — Integrated Gas Control (IGC) Board
Table 15 — IGC Connections
POINT DESCRIPTION
Input power from TRAN 1
Speed sensor
Flame sensor
Heat stage 1
Rollout switch
Limit switch
Induced draft combustion
motor
Indoor fan
Gas valve (heat stage 1)
SENSOR LOCATION
control box
gas section
gas section
LCTB
gas section
fan section
gas section
control box
gas section
41
RED LED - STATUS
CONNECTION
TYPE OF I/O
24 vac
analog input
switch input
24 vac
switch input
switch input
switch input
line VAC
relay
relay
PIN NUMBER
J1, 1-3
J2, 2
J2, 5-6
J2, 7-8
J2, 9-10
J2, 1
J2, 11-12

Advertisement