X609 Terminal Strip - Siemens SINAMICS S120 Equipment Manual

Air-cooled chassis power units
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Line-side power components
4.7 Active Interface Modules Chassis-2
4.7.3.6

X609 terminal strip

Table 4- 34
X609 terminal strip
Connector
Terminal
PE
1
2
3
4
5
6
7
8
9
10
11
12
13
14
PE
Max. connectable cross-section: 2.5 mm
Note
Cable gland and cable holder
Under terminal X609, there is a cable gland in the front cover and cable holders for securing
the cables.
NOTICE
Device failure due to overtemperature caused by faulty wiring
During operation, Active Interface Modules require a signal to terminal X609:9 and X609:10
for fan activation. If this signal is not present during operation, the fans do not rotate and
the module is shut down on overtemperature.
• Connect the signals to terminal X609:9 and X609:10 on the Active Interface Module
110
Designation
PE
P24
P24
M
M
L
L
N
N
Control of fan contactor
Control of fan contactor
NC
NC
NC
NC
PE
2
Chassis-2 for fan activation.
Technical specifications
PE connection
External 24 V DC supply
Voltage: 24 VDC (20.4 ... 28.5 V)
Current consumption: Max. 0.25 A
Voltage: 230 VAC (195.5 ... 264.5 V)
Current consumption: Max. 10 A
Fan operating currents, see "Technical data"
Voltage: 230 VAC
(195.5 ... 264.5 V)
Current consumption: Max. 4 A
Reserved, do not use
Reserved, do not use
Reserved, do not use
Reserved, do not use
PE connection
to Active Line Module Chassis-2,
X9:HS1
to Active Line Module Chassis-2,
X9:HS2
Air-cooled chassis power units
Manual, 07/2019, 6SL3097-4AE00-0BP9