Technical Data; Active Line Modules Chassis-2, 380 - Siemens SINAMICS S120 Equipment Manual

Air-cooled chassis power units
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Line Modules
5.5 Active Line Modules Chassis-2
5.5.8

Technical data

5.5.8.1
Active Line Modules Chassis-2, 380 ... 480 V 3 AC
Table 5- 55
Technical data for Active Line Modules Chassis-2, 380 ... 480 V 3 AC
Article number
Rated power
- For I
(50 Hz, 400 V)
n_DC
- For I
(50 Hz, 400 V)
L_DC
- For I
(60 Hz, 460 V)
n_DC
- For I
(60 Hz, 460 V)
L_DC
DC link current
- Rated current I
n_DC
- Base load current I
L_DC
- Maximum current I
max_DC
Infeed/regenerative feedback current
- Rated current I
n_E
- Maximum current I
max_E
Supply voltages
- Line voltage
- Line frequency
- Electronic power supply
- DC-link voltage
Pulse frequency
Current consumption
- Electronics current consumption (24 VDC)
- Total fan current consumption
(at 400 VAC)
Max. ambient temperature
- Without derating
- With derating
DC link capacitance
- Active Line Module
- Drive group, max.
- at 400 V / 50 Hz
1)
- at 480 V / 60 Hz
1)
Power loss
2)
- At 50 Hz 400 V
- At 60 Hz 460 V
Cooling air requirement
Sound pressure level
L
(1 m) at 50/60 Hz
pA
Connections
- Line connection (U1, V1, W1)
- DC-link connection (DCP, DCN)
- PE connection
Max. connection cross-sections
- Line connection (U1, V1, W1)
- DC-link connection (DCP, DCN)
- PE connection
246
6SL3331– 7TE35–6AA0
kW
355
kW
300
HP
500
HP
400
A
630
A
571
A
857
A
560
A
773
V
3AC 380 -10% (-15% < 1 min) ... 3AC 480 +10%
ACrms
Hz
V
DC
V
DC
kHz
4
A
1.3
A
1.8
° C
45
° C
60
µF
16450
µF
130000/400000/not permissible
µF
95000/250000/not permissible
kW
4.47
kW
4.48
m
/s
0.64
3
dB(A)
72.5
4 x M12
2 x M12
4 x M12
mm²
4 x 240
mm²
busbar
mm²
4 x 240
7TE36–4AA0
7TE38–8AA0
400
560
350
500
550
800
500
700
710
1010
649
915
974
1373
635
900
878
1238
47 ... 63Hz
24 (20.4 ... 28.8)
1.5 x U
line
4
4
1.3
1.3
1.8
1.8
45
45
60
60
not permissible/400000/630000
not permissible/250000/450000
4.47
7.13
4.48
7.14
0.64
0.64
72.5
72.5
4 x M12
6 x M12
2 x M12
4 x M12
4 x M12
6 x M12
4 x 240
6 x 240
busbar
Busbar
4 x 240
6 x 240
Air-cooled chassis power units
Manual, 07/2019, 6SL3097-4AE00-0BP9
7TE41–0AA0
630
560
900
800
1100
1004
1506
985
1358
4
1.3
1.8
45
60
25900
7.86
7.87
0.64
72.5
6 x M12
4 x M12
6 x M12
6 x 240
Busbar
6 x 240