NOTICE
Damage to the Voltage Peak Limiter due to interchanged connections
The Voltage Peak Limiter will be damaged if the input and output connections are
interchanged.
• Connect the incoming cable from the DC link of the Motor Module to DCPS, DCNS.
• Connect the incoming cable from the DC link of the Motor Module Chassis-2 to DCP,
• Connect the outgoing cable for the dV/dt reactor to 1U2, 1V2, 1W2.
NOTICE
Damage to the dV/dt filter by using components that have not been released
When using components that have not been released, damage or malfunctions can occur
at the devices or the system itself.
• Only use dV/dt filters that SIEMENS has released for operation with SINAMICS.
NOTICE
Damage to the dV/dt filter by exceeding the maximum output frequency
The maximum permissible output frequency when using a dv/dt filter is 150 Hz. The dV/dt
filter can be damaged if the output frequency is exceeded.
• Operate the dv/dt filter with a maximum output frequency of 150 Hz.
NOTICE
Damage to the dV/dt filter by exceeding the maximum pulse frequency
The maximum permissible pulse frequency when using a dv/dt filter is 2.5 kHz or 4 kHz.
The dV/dt filter can be damaged if the pulse frequency is exceeded.
• When using the dv/dt filter, operate the Motor Module with a maximum pulse frequency
NOTICE
Damage to the dV/dt filter if it is not activated during commissioning
The dV/dt filter may be damaged if it is not activated during commissioning.
• Activate the dv/dt filter during commissioning via parameter p0230 = 2.
Air-cooled chassis power units
Manual, 07/2019, 6SL3097-4AE00-0BP9
DCN.
of 2.5 kHz or 4 kHz.
Motor-side power components
9.3 dv/dt filter plus Voltage Peak Limiter