Siemens SINAMICS S120 Equipment Manual page 152

Air-cooled chassis power units
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Line Modules
5.2 Basic Line Modules
Table 5- 14
Technical data for Basic Line Modules, 3 AC 380 V ... 480 V, Part 2
Article number
Rated output
- For I
(50 Hz, 400 V)
n_DC
- For I
(50 Hz, 400 V)
H_DC
- For I
(60 Hz, 460 V)
n_DC
- For I
(60 Hz, 460 V)
H_DC
DC-link current
- Rated current I
n_DC
- Base load current I
H_DC
- Maximum current I
max_DC
Input current
- Rated current I
n_E
- Maximum current I
max_E
- Maximum precharging current (max. 3 s)
Supply voltages
- Line voltage
- Line frequency
- Electronic power supply
- Fan supply voltage
- DC-link voltage
Current consumption
- Electronics current consumption (24 VDC)
- Fan power consumption (230 VAC)
Max. ambient temperature
- Without derating
- With derating
DC-link capacitance
- Basic Line Module
- Drive line-up, max.
Power loss, max.
1)
- at 50 Hz 400 V
- at 60 Hz 460 V
Cooling air requirement
Sound pressure level
L
(1 m) at 50/60 Hz
pA
Line/load connection
Max. connection cross-sections
- Line connection (U1, V1, W1)
- DC-link connection (DCP, DCN)
- PE connection
Max. cable length
(total of all motor cables and DC link)
- Shielded
- Unshielded
Degree of protection
150
6SL3330– 1TE41–5AA3
kW
710
kW
560
HP
1090
HP
860
A
1500
A
1170
A
2250
A
1265
A
1897
A
internal
V
3 AC 380 -10% (-15% < 1 min) ... 3 AC 480 +10%
ACrms
Hz
V
DC
V
AC
V
1.35 x U
DC
A
1.1
A
4.5
° C
40
° C
55
µF
29000
µF
232000
kW
5.5
kW
5.5
m
/s
0.36
3
dB(A)
71 / 73
M12
mm²
6 x 185
mm²
6 x 185
mm²
4 x 240
m
4000
m
6000
IP00
1TE41–8AA3
900
705
1390
1090
1880
1467
2820
1630
2380
308
47 ... 63 Hz
24 (20.4 ... 28.8)
230 (195.5 ... 264.5)
(partial load) / 1.32 x U
line
1.1
4.5
40
55
34800
139200/
278400
4)
6.9
6.9
0.36
71 / 73
Flat connector for screw
M12
6 x 185
6 x 185
4 x 240
4800
7200
IP00
Air-cooled chassis power units
Manual, 07/2019, 6SL3097-4AE00-0BP9
(full load)
line

Advertisement

Table of Contents
loading

Table of Contents