HEATING SEQUENCE OF OPERATION
NORMAL AND ABNORMAL
HEATING MODE
I
POWER ON
I
CONTROL SELF-CHECK
OKAY?
1
POLARITY
OKAY?
YES
IS THERE A
PROPER GROUND?
YES
_
I._
POLARITY
REVERSED,
STATUS ERROR CODE 5 + 4,
.__.1
SIGNAL HOLDS UNTIL UNIT IS PROPERLY GROUNDED.
STATUS ERROR CODE 5 + 3.
A
NORMAL
OPERATION:
STATUS LED -- PULSE
,1
B
GAS VALVE OFF. COMBUSTION
AIR INDUCER OFF.
INDOOR BLOWER OFF. (RESET CONTROL
BY
TURNING MAIN POWER OFF.)
COMBUSTION
AIR INDUCER OFF.
INDOOR BLOWER ON. HAS PRIMARY OR
THERMOSTAT
CALLS FOR HEAT:
STATUS LED -- HEARTBEAT
YES
PRIMARY AND SECONDARY
LIMIT
SWITCHESyEs _ LOSED?
ROLLOUT SWITCH CLOSED?
YES
_
FIRST (LOW) STAGE PRESSURE
SWITCH
[.NO
CONTACTS OPEN?
YES
_
I
SECOND
(HIGH)coNTACTS
YES
STAGE _ PRESSURE
OPEN?
SWITCH
I_
r
I
I
TWO-STAGE
OR SINGLE-STAGE
THERMOSTAT
i._..._
L
CALL FOR HEAT
1
STATUS LED -- HEARTBEAT
I
CONTINUED ON NEXT PAGE
I
60-MINUTE LIMIT WATCHGUARD
MODE.
GAS VALVE OFF, COMBUSTION
AIR INDUCER
OFF, INDOOR BLOWER OFF WITH DELAY.
STATUS ERROR CODE 4 + 5.
/
SECONDARY
LIMIT RESET WITHIN 3 MINUTES?
I y_:.q
STATUS ERROR CODE 3 + 1.
GAS VALVE OFR COMBUSTION
AIR INDUCER ON.
INDOOR BLOWER ON.
STATUS ERROR CODE 5 + 1.
SEQUENCE
HOLDS UNTIL ROLLOUT SWITCH IS
RESET AND MAIN POWER IS INTERRUPTED
OR
T'STAT IS CYCLED OFF/ON FOR 3 SEC. MINIMUM,
GAS VALVE OFF. COMBUSTION
AIR INDUCER OFR
INDOOR BLOWER OFR CONTROL REMAINS UNTIL
PRESSURE
SWITCH
IS DETECTED OPEN.
STATUS ERROR CODE 2 + 4
GAS VALVE OFR
COMBUSTION
AIR INDUCER OFF.
INDOOR BLOWER OFR
CONTROL WILL NOT ATTEMPT SECOND-STAGE
OPERATION
DURING THIS HEAT DEMAND.
FIRST-STAGE
OPERATION WILL BE ATTEMPTED.
STATUS ERROR CODE 2 + 6.
YES
Page 44