Lennox G60UHV Series Installation Instructions Manual page 41

Hide thumbs Also See for G60UHV Series:
Table of Contents

Advertisement

G60UHV(X) BURNER & HEAT EXCHANGER
REMOVAL
HEATEXCHANGER
GASKET
BOX
ASSEMBLY
GAS VALVE
ASSEMBLY
FIGURE 28
NOxlNSERTS
(X modelsonly)
/
FIGURE 29
10- Repeat procedure for each heat exchanger section.
11- After each of the top heat exchanger sections has been
cleaned, insert the brush end of the cable snake into
the bottom openings of each of the heat exchanger
sections and clean as described in step 8.
12- Remove the cable from the heat exchanger. Use a vac-
uum cleaner to remove debris knocked loose during
cleaning.
13- Attach the exhaust end (positive pressure) of the vacu-
um cleaner to the top of the heat exchanger section.
Any loose debris will be forced to the bottom of the heat
exchanger section. Vacuum debris from bottom open-
ings.
14- Replace collector box and combustion air inducer.
Check gaskets for damage. Damaged gaskets must be
replaced to avoid heat exchanger leaks. Replace all
screws to the collector box and combustion air inducer.
Failure to replace all screws may cause leaks.
15- To clean the burner, run a vacuum cleaner with a soft
brush attachment over the face of burners. Visually in-
spect inside the burners and crossovers for any blockage
caused by foreign matter. Remove any blockage.
16- NOx units only - Reattach the NOx inserts to the cor-
bels at the entrance to each heat exchanger opening.
See figure 29.
17- Re-install gasket and burner box / manifold assembly
onto the vestibule panel. Replace burner box cover
and re-secure using screws.
NOTE - Gasket must be replaced if it was damaged
during disassembly.
18- Reconnect wires to pressure switch, roll-out switches,
gas valve and combustion air inducer. Refer to unit wir-
ing diagram.
19- Re-install top cap and re-secure vent pipe to combus-
tion air inducer outlet.
20- Reconnect gas supply piping.
21- Turn on power and gas supply to unit.
22- Set thermostat and check for proper operation.
23- Check all piping connections, factory and field, for gas
leaks. Use a leak detecting solution or other preferred
means,
CAUTION
24- Ira leak is detected,
shut gas and electricity
offand
repair leak.
25- Repeat steps 23 and 24 until no leaks are detected.
26- Replace front access panel.
Page 41