Operating Sequence - Lennox G60UHV Series Installation Instructions Manual

Hide thumbs Also See for G60UHV Series:
Table of Contents

Advertisement

TABLE 26
G60UHV-60D-135
BLOWER MOTOR PERFORMANCE
0.0" to 0.8" w.g. (0 through 200 Pa) External Static Pressure Range
Factory Settings: Heating Speed - 2; Cooling Speed - 4; Speed Adjust - NORM.
Return Air Options: Side return air with optional RAB return air base.
"ADJUST"
Switch
Positions
Speed Switch Positions
Second Stage "HEAT" Speed
Second Stage "COOL"
Speed
1
2
3
4
1
2
3
4
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
+
1425
675
1615
760
1795
845
1975
930
1505
710
1620
765
1815
855
2035
960
NORM
N/A
N/A
1455
690
1640
775
1805
850
1370
650
1470
695
1670
790
1850
875
--
N/A
N/A
N/A
N/A
1455
685
1630
770
1225
580
1320
625
1500
705
1670
790
"ADJUST"
First Stage "HEAT" Speed
First Stage "COOL"
Speed
Switch
1
2
3
4
1
2
3
4
Positions
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
+
1305
615
1470
695
1655
780
1825
860
1075
510
1155
545
1295
610
1445
680
NORM
N/A
N/A
1345
635
1505
710
1670
790
980
465
1050
495
1175
555
1305
615
--
N/A
N/A
N/A
N/A
1340
635
1475
695
875
415
935
440
1070
505
1180
555
N/A - First and second stage HEAT positions shown cannot be used on this model.
NOTES - The effect of static pressure is included in air volumes shown.
First stage HEAT is approximately
91% of the same second stage HEAT speed position.
First stage COOL (two-stage air conditioning
units only) is approximately
70% of the same second stage COOL speed position.
Continuous
Fan Only speed is approximately
38% of the same second stage COOL speed position - minimum 500 cfm (235 L/s).
Lennox Harmony Ill ' Zone Control Applications
- Minimum blower speed is 495 cfm (235 L/s).
TABLE 27
OPERATING
SEQUENCE
G60UHV,
Thermostat
with Humidity
Control
Feature
and Single-Speed
Outdoor
Unit
OPERATING
t
'
t
.......
S¥S
EM DEMAND
S¥S
EM RESPONSE
SEQUENCE
.
Thermostat
Demand
Relative
Humidity
System
Step
I
III
Condition
Y1
O
G
W
1
Status
D
NO CALL
FOR DEHUMIDIFICATION
Normal Operation
1
On
On
On
BASIC MODE (only active on a Y1 thermostat demand)
Normal Operation
1
On
On
On
Dehumidification
2
On
On
On
On
Call
Compres-
sor
24
Acceptable
VAC
High
24
Acceptable
VAC
High
0
Demand
VAC
High
Blower
CFM
(COOL)
lOO%
lOO%
70%
Comments
Compressor and indoor
blower follow thermostat
demand
SignatureStat T" thermo-
stat energizes Y1 and de-
energizes D on a call for
de-humidification
PRECISION
MODE
(operates
ind_ oendent
of a Y1 thermostat
demand)
Normal Operation
Dehumidification
call
Dehumidification
call ONLY
24
1
On
On
On
Acceptable
VAC
High
0
2
On
On
On
Demand
VAC
High
0
1
On
On
On
Demand
VAC
High
Jumpers at indoor unit with a single stage outdoor unit
With Condensing unit - Cut W914 (R to DS) on SureLight board
With Heat Pump - Cut W914 (R to DS) & W951 (R to O) on SureLight board
100%
70%
70%
Dehumidification
mode
begins when humidity is
greater than set point
SignatureStat
T`' thermo-
stat will try to maintain
room humidity
setpoint
by
allowing
the room space
to maintain
a temperature
that is cooler
than the
room thermostat
setpoint*
Thermostat used: 51M26 -- 1 heat/1
cool or 51M28 -- 2 heat/2
cool for heat pumps
*In Precision mode, SignatureStat "thermostat
will allow room temperature up to 2 °F (1.2°C) cooler than room temperature
setting in order to meet humidity control demand.
Page 35