Commissioning, inspection, maintenance

Installing the burner

4x
F
D
C
B
A
Fig. 45
1. If necessary, move the programming unit.
2. Insert the burner. Tighten screws
Torque: 6.5 Nm
3. Fit gas supply pipe
E
Torque: 30 Nm
4. Check the gas connections for leaks.
Danger
Escaping gas leads to a risk of explosion.
Check all fittings for gas tightness. In the
case of wall mounted appliances, also check
the gas shut-off valve fitting on the under-
side.

Checking the neutralising system (if installed)

58
E
diagonally.
F
with a new gasket.
5. Connect the cables/leads:
Fan motor
(2 plugs)
A
Ionisation electrode
Ignition unit
C
Earth
D
B