Cleaning The Heating Surfaces; Checking The Condensate Drain And Cleaning The Trap - Viessmann VITODENS 200-W Installation And Service Instructions For Contractors

1.9 to 32 kw, wall mounted gas condensing boiler with 7 inch colour touchscreen, natural gas and lpg version
Table of Contents

Advertisement

Commissioning, inspection, maintenance
Checking the back draught safety devices
1. Remove the balanced flue system.
Note
If the balanced flue system cannot be removed,
clean and check the back draught safety device via
the inspection cover.
2. Check back draught safety device
of movement and function.

Cleaning the heating surfaces

!
Please note
Scratches to the surfaces of the heat exchanger
that come into contact with hot gas can result in
corrosion damage. Brushing can cause deposits
to become lodged in the gaps between the coils.
Never use brushes to clean the heating sur-
faces.
!
Please note
Prevent damage due to cleaning water.
Cover electronic components with suitable
watertight material.
Note
Discolouration on the heat exchanger surface is a nor-
mal sign of use. It has no bearing on the function and
service life of the heat exchanger.
The use of chemical cleaning agents is not required.

Checking the condensate drain and cleaning the trap

!
Please note
Prevent damage due to condensate.
Cover electronic components with suitable
watertight material.
56
3. Refit the balanced flue system.
4. Pour a small amount of water through the inspec-
tion port to ensure the back draught safety device
is working.
A
for dirt, ease
A
Fig. 43
1. Use a vacuum cleaner to remove combustion resi-
dues from heating surface
exchanger.
2. Flush heating surface
3. Check condensate drain. Clean the trap: See the
following chapter.
(cont.)
A
of the heat
with water.
A