Installing The Burner - Viessmann Vitosorp 200-F Installation Instructions For Contractors

Gas adsorption heating appliance natural gas and lpg version
Hide thumbs Also See for Vitosorp 200-F:
Table of Contents

Advertisement

Commissioning, inspection, maintenance
Checking the condensate drain and cleaning the...
B
A
C
2.
Fig. 42
Filler pipe
B

Installing the burner

G
4x
C
D
E
B
A
Fig. 43
56
1. Check at the trap that the condensate can drain
freely.
5. Remove the condensate hoses from lute
6. Clean the trap.
7. Fill siphon with water and reassemble with retain-
ing clip
8. Check that the condensate hoses are connected
correctly to the siphon and heat exchangers.
3.
Note
Route the drain hose without any bends and with a
constant fall.
4.
1. Insert the burner and tighten screws
Torque: 8.5 Nm
2. Fit gas supply pipe
Torque: 30 Nm
3. Check gas connections for tightness.
F
4. Connect the electrical cables/leads:
Fan motor
Ionisation electrode
Gas train
Ignition unit
Earth
(cont.)
.
A
with a new gasket.
F
Danger
Escaping gas leads to a risk of explosion.
Check the fitting for gas tightness.
A
C
B
D
E
.
C
G
crosswise.