Commissioning, inspection, maintenance
Checking the condensate drain and cleaning the...
B
A
C
2.
Fig. 42
Filler pipe
B
Installing the burner
G
4x
C
D
E
B
A
Fig. 43
56
1. Check at the trap that the condensate can drain
freely.
5. Remove the condensate hoses from lute
6. Clean the trap.
7. Fill siphon with water and reassemble with retain-
ing clip
8. Check that the condensate hoses are connected
correctly to the siphon and heat exchangers.
3.
Note
Route the drain hose without any bends and with a
constant fall.
4.
1. Insert the burner and tighten screws
Torque: 8.5 Nm
2. Fit gas supply pipe
Torque: 30 Nm
3. Check gas connections for tightness.
F
4. Connect the electrical cables/leads:
■
Fan motor
■
Ionisation electrode
Gas train
■
■
Ignition unit
■
Earth
(cont.)
.
A
with a new gasket.
F
Danger
Escaping gas leads to a risk of explosion.
Check the fitting for gas tightness.
A
C
B
D
E
.
C
G
crosswise.