Installation sequence
Electrical connections
Connecting the low loss header sensor
The sensor of the low loss header is connected to the
accessory extension EM-P1 or EM-M1/MX (ADIO elec-
tronics module) respectively.

Connecting the cylinder temperature sensor

Connect the cylinder temperature sensor to terminals 3
and 4 on external plug
C

Connecting the circulation pump to P1 and P2

Note
Observe the priority of the connections.
M
A
1~
B
Fig. 16
Circulation pump
A
P1/P2 plug on HMU heat management unit
B
Possible connections to P1 and priority of connections:
1. Circulation pump for cylinder heating
2. If no circulation pump for cylinder heating is present:
Heating circuit pump for heating circuit without mixer
A1 in connection with low loss header and heating
circuits with mixer

Floating switching contact connection

Connection at plug
lH
One of the following functions can be connected:
External demand
External blocking
DHW circulation pump external demand (pushbutton
function, pump runs for 5 min). Not for
Vitodens 222-W.
Room temperature controller (room thermostat)
In conjunction with operating mode Continuous oper-
ation with room temperature controller (not for
Vitodens 3xx)
External heating circuit hook-up (if installed), see
page 120
Not for Vitodens 3xx.
26
(cont.)
)
. See page 24.
See installation instructions for extension EM-P1
or EM-M1/MX
Possible connections to P2 and priority of connections:
1. Heating circuit pump for heating circuit without mixer
A1 in connection with low loss header and heating
circuits with mixer
2. If no circulation pump for heating circuit without
mixer is present:
DHW circulation pump
Note
If a heating circuit pump for heating circuit without
mixer is installed, connect the DHW circulation
pump to the P1 extension (accessories).
Connect DHW circulation pumps with standalone
functions directly to the 230 V ∼ supply.
The function of connections P1 and P2 is selected in
the commissioning assistant by selecting the connec-
ted component in the system scheme.
Specification
Rated current
Rated voltage
A
1 L
N
?
lH
Fig. 17
Floating contact
A
1 A
230 V ~