CHAPTER 3 INSTALLATION

1 Engineering Installation Preparation and
Notice

1.1 Installation Notice

Personnel and property safety are highly concerned during the entire installation process.
Installation implementation must abide by relevant national safety regulations to ensure personnel and
property safety.
All personnel involved in the installation must attend safety education courses and pass
corresponding safety examinations before installation. Only qualified personnel can attend the
installation. Relevant personnel must be held responsible for any violation of the regulation.

1.2 Installation Key Points and Importance

VRF air conditioning systems use refrigerant, instead of other agent, to directly evaporate to carry
out the system heat. High level of pipe cleanness and dryness is required in the system. Since various
pipes need to be prepared and laid out onsite, carelessness or maloperation during installation may
leave impurities, water, or dust inside refrigerant pipes. If the design fails to meet the requirement,
various problems may occur in the system or even lead to system breakdown.
Problems that usually occur during installation are as follows:
No.
Installation Problem
Dust or impurities enter into
1
the refrigeration system.
Nitrogen is not filled into the
refrigerant pipe or
2
insufficient Nitrogen is filled
before welding.
The vacuum degree in the
3
refrigerant pipe is
insufficient.
Water enters into the
4
refrigeration system.
The refrigerant pipe
specifications do not meet
5
the configuration
requirements.
6
Refrigerant pipe is blocked.
Refrigerant pipe exceeds
7
the limit.
Incorrect amount of
8
refrigerant is filled.
9
The refrigerant pipe leaks.
Water drainage from the
10
condensate water pipe is
not smooth.
Pipes are more likely to be blocked; air conditioning performance is reduced;
compressor wear is increased or even hinder the normal operation o f the system
and burn the compressor.
Pipes are more likely to be blocked; air conditioning performance is reduced;
compressor wear is increased or even hinder the normal operation of the system
and burn the compressor.
The refrigeration performance is reduced. The system fails to keep normal
operation due to frequent protection measures. When the problem getting
serious, compressor and other major components can be damaged.
Copper plating may appear on the compressor and reduce the compressor
efficiency with abnormal noise generated; failures may occur in the system due
to ice plug.
Smaller configuration specifications can increase the system pipe resistance and
affect the cooling performance; larger configuration specifications are waste of
materials and can also reduce the cooling performance.
The cooling performance is reduced; in certain cases, it may cause long -term
compressor operating under overheat conditions; the lubricating effe ct can be
affected and the compressor may be burnt if impurities were mixed with the
lubricating oil.
The loss in pipe is considerable and the unit energy efficiency decreases, which
are harmful for long-term running of the system.
The system cannot correctly control the flow allocation; the compressor may be
operating under over-heating environment or running when the refrigerant flows
back to the compressor.
Insufficient refrigerant circulating in the system decreases the cooling
performance of the air conditioner. Long-term operation under such circumstance
may cause an overheating compressor or even damage the compressor.
Residual water in IDUs can affect the normal operation of the system. The
possible water leakage can damage the IDU's decoration.
70
Possible Consequence