Gree GMV-ND07PLS/A-T(U) Service Manual page 54

Multi variable air conditioners indoor unit for north america
Hide thumbs Also See for GMV-ND07PLS/A-T(U):
Table of Contents

Advertisement

Multi Variable Air Conditioners Indoor Unit for North America
parameter value settings. The parameter value blinks. Adjust the parameter value by pressing ― ‖ or ― ‖
and then press the ―ENTER/CANCEL‖ button to complete settings.
(3) Press the ―ENTER/CANCEL‖ button to return to the upper-level menu till quitting parameter
settings.
The user parameter setting list is as follows:
Parameter
Parameter
Code
Name
Master IDU
P10
settings
Infrared
connection
P11
settings of
wired controller
Wired
controller
P13
address
settings
One wired
controller
controls
P14
multiple IDUs
quantity
settings
Static pressure
P30
settings for
indoor fan
High-ceiling
P31
installation
Timer function
P33
settings
Repeating
validity for
P34
time-point
timing
P37
Cooling setting
Table 4.2 User Parameter Setting List
Parameter Range
00: does not change the
master/slave status of
the current IDU
01: sets the current IDU
to master IDU
00: disabled
01: enabled
01: master wired
controller
02: slave wired
controller
00: disabled
01-16: number of indoor
units
Type 1: 03.04.05.06.07
Type 2:
01.02.03.04.05.06.07.08
.09
00: standard-ceiling
installation height
01: high-ceiling
installation height
00: count down timing
01: time-point timing
00: single timing
01: repeated everyday
17° C -30° C
48
Default
Value
After the IDU connected
with the current wired controller is
00
successfully set to master IDU, "MASTER"
on the wired controller is on.
This setting can only be enabled through
the master wired controller.
When the infrared remote receiving
function of the wired controller is disabled,
01
neither the master nor slave wired
controller can receive remote signals. The
wired controllers can only be operated by
pressing.
When two wired controllers simultaneously
control one or more IDUs, the two wired
controllers should use different addresses.
01
The slave wired controller (address: 02)
does not have the unit parameter setting
function except its own address settings.
This value is set based on the number of
connected IDUs.
01
If the current value is inconsistent with the
actual number of group-controlled IDUs, an
―L9‖ fault may occur.
After identifying the IDU type, the wired
controller only displays the available static
pressure levels.
①. The static pressure levels fall into five
levels and nine levels for VRF IDUs.
Wired controller can be adapted to the
different types of indoor units that it
possesses 1-9 level selection for
setting static pressure.If the static
05
pressure levels received by the IDU
from the wired controller, remote
controller, or remote monitoring
system exceed the setting range, the
limit value prevails.
②. During power-on and synchronization,
the setting value of static pressure
levels is determined by settings of the
IDU.
00
Only applicable to cassette units
00
This setting is valid only when the timer
00
function is set to time-point timing.
Cooling setting temperature – heating
25
Remark