2 After-sales Emergency Masures

When some unrecoverable fault occurs to one module which is connected with several others in
parallel, the following emergency measures are recommended to guarantee the heating or cooling
capacity of the indoor units and the service life of modules except the faulted one are not affected.
Step 1: set all indoor units under ―Off‖ mode and cut off the power supply to the indoor and outdoor
units.
Step 2:.shut off all cutoff valves of the faulted outdoor unit, including the cutoff valves of the
liquid/gas pipe as well as the oil balancing valve.
Step 3: cut off the air switch of the module.
Step 4: remove the communication line between the faulted module and other modules which are
still kept connected through the communication line.
Step 5: readjust the address and quantity settings on the main board of the modules except the
faulted one.
Step 6: power and restart the unit.

3 Wiring Diagram

NOTICE!
This drawing is just for reference; please always refer to the electric wiring stuck to the unit for
actual wiring.

3.1 Low Static Pressure Duct Type Indoor Unit

Model:GMV-ND07PLS/A-T(U) ~ GMV-ND22PLS/A-T(U)
Multi Variable Air Conditioners Indoor Unit for North America